User Manual

79
Measurement
Measurement range
(with unity ratio)
Display resolution
(with unity ratio)
Maximum intrinsic error
Minimum Maximum
RMS
harmonic
voltage
(order n 2)
simple 2 V 1000 V
(1)
100 mV
V < 1000 V
±(2.5 % + 1 V)
1 V
V 1000 V
compound 2 V 2000 V
(2)
100 mV
U < 1000 V
±(2.5 % + 1 V)
1 V
U 1000 V
RMS
distortion
voltage
simple (Vd) 2 V 1000 V
(1)
100 mV
V < 1000 V
±(2.5 % + 1 V)
1 V
V 1000 V
compound (Ud) 2 V 2000 V
(2)
100 mV
U < 1000 V
±(2.5 % + 1 V)
1 V
U 1000 V
RMS
harmonic
current
(order n 2)
J93 clamp 1 A 3500 A 1 A
±(2 % + (n x 0.2%) + 1 A)
n 25
C193 clamp
PAC93 clamp
1 A 1000 A
100 mA
A < 1000 A
±(2 % + (n x 0.2%) + 1 A)
n 25
1 A
A 1000 A
±(2 % + (n x 0.5%) + 1 A)
n > 25
MN93 clamp 200 mA 200 A 100 mA
±(2 % + (n x 0.2%) + 1 A)
n 25
±(2 % + (n x 0.5%) + 1 A)
n > 25
E3N clamp (10 mV/A)
MN93A clamp (100 A)
100 mA 100 A
10 mA
A < 100 A
±(2 % + (n x 0.2%) + 100 mA)
n 25
100 mA
A 100 A
±(2 % + (n x 0.5%) + 100 mA)
n > 25
E3N clamp (100 mV/A) 10 mA 10 A
1 mA
A < 10 A
±(2 % + (n x 0.2%) + 10 mA)
n 25
10 mA
A 10 A
±(2 % + (n x 0.5%) + 10 mA)
n > 25
MN93A clamp (5 A)
5 A adapter
Essailec
®
adapter
5 mA 5 A 1 mA
±(2 % + (n x 0.2%) + 10 mA)
n 25
±(2 % + (n x 0.5%) + 10 mA)
n > 25
AmpFLEX™ A193
MiniFLEX MA193
(10 kA)
10 A 10 kA
1 A
A < 10 kA
±(2 % + (n x 0.3%) + 1 A + (Afrms
(3)
x 0.1%))
n 25
10 A
A 10 kA
±(2 % + (n x 0.6%) + 1 A + (Afrms
(3)
x 0.1%))
n > 25
AmpFLEX™ A193
MiniFLEX MA193
(6500 A)
10 A 6,500 A
100 mA
A < 1,000 A
±(2 % + (n x 0.3%) + 1 A + (Afrms
(3)
x 0.1%))
n 25
1 A
A 1,000 A
±(2 % + (n x 0.6%) + 1 A + (Afrms
(3)
x 0.1%))
n > 25
AmpFLEX™ A193
MiniFLEX MA193
(100 A)
100 mA 100 A
10 mA
A < 100 A
±(2 % + (n x 0.2%) + 30 pt)
n 25
100 mA
A 100 A
±(2 % + (n x 0.5%) + 30 pt)
n > 25
(1) In 1,000 Vrms, category III, provided that the voltage between each of the terminals and earth does not exceed 1,000 Vrms.
(2) Two-phase (opposite phases) – same note as (1).
(3) RMS value of the fundamental.