User Manual
44
7.3.3. THE 4A CF DISPLAY SCREEN
This screen displays the current waveforms of one period and the peak factors.
Figure 62: The 4A CF display screen
Note: L1, L2 and L3 display the current and voltage peak factors for phases 1, 2 and 3, respectively.
7.4. MEASUREMENT OF EXTREME AND MEAN VOLTAGE AND CURRENT
The sub-menu displays the one-second mean and half-cycle maximum and minimum RMS voltage and current and the in-
stantaneous positive and negative peak voltage and current.
Note: The MAX. and MIN. RMS measurements are calculated every half cycle (i.e. every 10 ms for a 50-Hz signal). The measure-
ments are refreshed every 250 ms.
The RMS measurements are calculated over one second.
7.4.1. THE 3U MAX.-MIN. DISPLAY SCREEN
This screen displays the one-second mean and half-cycle maximum and minimum RMS values and the positive and negative
phase-to-phase voltage peaks.
Peak factor for each curve.
Current axis with automatic scaling.
Instantaneous value cursor. Use the
or key to move the cursor.
Instantaneous values of the signals
at the position of the cursor.
t: time relative to the start of the
period.
A1: instantaneous current of phase 1.
A2: instantaneous current of phase 2.
A3: instantaneous current of phase 3.
AN: instantaneous value of the cur-
rent of the neutral.
Columns of values for each curve (1, 2, and 3).
MAX: maximum RMS phase-to-phase voltage since the switching on of the
device or since the last time the
key was pressed.
RMS: true RMS phase-to-phase voltage.
MIN: minimum RMS phase-to-phase voltage since the switching on of the device
or since the last time the
key was pressed.
PK+: maximum (positive) peak phase-to-phase voltage since the switching on
of the device or since the last time the
key was pressed.
PK-: minimum (negative) peak phase-to-phase voltage since the switching on of
the device or since the last time the
key was pressed.
Figure 63: The 3U Max.-Min. display screen