User Manual

25
In the case of a 4-wire three-phase set-up, the neutral current sensor is simulated if the 3 phase sensors are identical.
The various current sensors are:
MN93 clamp: 200 A.
MN93A clamp: 100 A or 5 A.
C193 clamp: 1000 A.
J93 clamp : 3500 A.
AmpFLEX™ A193: 100, 6500 or 10000 A.
MiniFLEX MA193: 100, 6500 or 10000 6500 A.
PAC93 clamp: 1000 A.
E3N clamp: 100 A (sensitivity 10 mV/A).
E3N clamp: 10 A (sensitivity 100 mV/A).
Three phase adapter: 5 A or Essailec
®
.
If an MN93A clamp (5A range) or an Adapter is used, the current ratio setting is proposed automatically.
If an MN93A clamp (5A range), an Adapter, an AmpFLEX™, a MiniFLEX, or an E3N clamp is used, adjustment of the ratio, of the
range, or of the sensitivity is proposed automatically.
Use the arrow keys (,, , ) to define the transformation ratios between the primary current (1A to 60,000A) and the second-
ary current (1A, 2A or 5A), then validate with the
key.
The primary current cannot be less than the secondary current.
4.7.2. VOLTAGE RATIOS
A second screen V or U, defines the voltage ratios.
The programming of the ratio or ratios can be different or the same for all or for some channels.
The ratios to be programmed are phase-to-neutral voltage ratios when there is a neutral and phase-to-phase voltage ratios when
there is not.
To change the ratios, press the
key.
Figure 27: The Voltage Ratios screen in the Sensors and
ratios menu in the case of a set-up without neutral
Figure 28: The Voltage Ratios screen in the Sensors and
ratios menu in the case of a set-up with neutral
Use the arrow keys (,) to choose the configuration of the ratios.
3U 1/1 or 3V 1/1: all channels have the same 1/1 ratio.
3U or 3V: all channels have the same ratio, to be programmed.
Press the
key, then use the , keys to highlight the ratio in yellow.
Press the
key, then use the ,, and keys to change the ratio. The primary voltage is in kV and the secondary
voltage is in V.