Energy values, including
Tonnes Oil Equivalent
The Qualistar models measure energy.
This mode displays all the values
relating to power and energy.
“Start” and “Stop” keys
to activate and deactivate
summing of the energy values.
A new feature is the wide variety of units available:
kW, Joule, nuclear toe, non-nuclear toe, BTU, etc
Calculation of K factor for transformers
The harmonic currents owing in a network
lead to increased losses in the windings.
This results in heating of the transformer
and reduces the life span of the instruments
connected.
compliance with the NF EN 50464-3
standard for calculating transformer
derating.
the FHL and European K factor
parameters are recorded and measured
simultaneously.
Harmonics
All the useful parameters are
measured: global THD and
per phase on U, I, V and VA,
phase offset of harmonics.
Some models offer a VA
harmonics function and an
“expert mode”.
New: the harmonics measurement function is more comprehensive:
calculation of the harmonics in %f and %r
decomposition of the harmonics on the neutral conductor
calculation of the distorting voltages and currents
Distorting power
New!
Breakdown of the reactive power values,
with the concept of non-active power (N),
distorting power (D) and reactive power
(Q & Q
1
).
Breakdown of the reactive power
to nd the distorting power linked
to the harmonics (VAD).
Distorting power for sizing the harmonic
lters.
Reactive power (var) of the fundamental
for sizing the battery of the power-
correction capacitor.
Power and energy quality analysers