User Manual
18
6.5. INFLUENCES ON THE RESISTANCE MEASUREMENT
Quantities of influence Range of use
Variation of the measurement
Typical Maximum
Temperature -10 to + 55 °C 0,1 %/10 °C 0,5 %/10 °C + 2pt
Relative humidity 10 to 85 % RH @ 45°C 0,1 % 0,5 % + 2pt
Supply voltage 5 to 7 V 2 pt 0,2%/ V + 2pt
Series mode rejection, 50/60
Hz (1)
U (AC) = (Rmeasured x I
measurement)
< 0,2% 2% + 1pt
Common mode rejection, 50/60
Hz AC
0 to 50 V AC > 80 dB > 60 dB
(1) Example: If the measured resistance is 1 mΩ and the measurement current is 10 A, an alternating voltage of 1 mV RMS in
series with the resistance to be measured will induce an error of not more than 2%.
6.6. POWER SUPPLY
The instrument is powered by a rechargeable 6 V 8.5Ah NiMH battery pack. This has many advantages :
long life with small size and weight,
the possibility of recharging your battery rapidly,
a very small memory effect: you can recharge your battery rapidly, even if it is not fully discharged, without reducing its capacity,
protection of the environment: no polluting materials such as lead or cadmium.
The NiMH technology allows a limited number of charging/discharging cycles. The number depends on the conditions of use and
on the charging conditions. Under optimum conditions, the number of cycles is 200.
The instrument has 2 charging modes:
rapid charging: the battery recovers 90% of its capacity in 3h;
maintenance charging: this mode cuts in when the battery is very low and at the end of rapid charging.
The battery life depends on the ranges used
Number of measurements (1)
10 A range 850
1 A range 3 500
100 mA range 4 500
10 mA range 5 000
Instrument on standby or off battery life 4 to 6 months
(1) established for measurements lasting 5s, every 25s.
6.7. ENVIRONMENTAL CONDITIONS
Use indoors or outdoors.
Range of use - 10 to +55 °C 10 to 85 % RH
Storage (without battery) - 40 to +70 °C 10 to 90 % RH
Altitude < 2000 m
Degree of pollution 2
For long-term storage (2 years) with the battery, conditions must not depart from the range -20 to +30°C and 85% RH; otherwise,
the battery life will be degraded. For short-term storage (1 month), the temperature can reach 50°C.