User Instructions

Register Plate
With Soot Door
Alternative
Soot Door Positions
Fig. 11 Horizontal Register Plate With Top Flue Connection
Register Plate
With Soot Door
Alternative
Soot Door Positions
Fig. 10 Horizontal Register Plate With Rear Flue Connection
Register Plate
Soot Door
In Side or Rear
Of Chimney
Fig. 9 Vertical Register Plate With Bricked Up Fireplace
INSTALLATION INSTRUCTIONS
®
If it is found that there is excessive draw in the chimney then a
draught stabilizer should be fitted.
It is important that there is sufficient draw in the chimney and that
the chimney does not suffer from down-draught. When the chimney
is warm the draw should be not less than 0.05 inches water gauge
(12Pa). If in doubt about the chimney seek expert advice.
HEARTH AND FIRE SURROUND
The stove must stand on a fireproof hearth and combustible
materials must not be used in the construction of the fireplace unless
adequately fireproofed in accordance with local building regulations.
The hearth must be at least 12mm (0.5inches) thick. The positioning
of the stove and the size of the hearth are governed by building
regulations for Class 1 appliances. These building regulations state
that the hearth must extend in front of the stove by at least 225mm
(9 inches) and to the sides of the stove by at least 150mm (6
inches).Where possible it is helpful for the hearth to extend as far as
the doors when fully opened. If in doubt as to the positioning of the
stove expert advice should be sought either from the supplier or the
local building inspector.
The fireplace must allow good circulation of air around the appliance
to ensure that maximum heat is transferred to the room and also to
prevent the fireplace from overheating. A gap of 150mm (6 inches)
each side and 300mm (12 inches) above the appliance should give
sufficient air circulation. If a wooden mantelpiece or beam is used in
the fireplace it should be a minimum of 460mm (18 inches), and
preferably 600mm (24 inches) from the appliance. In some situations
it may be necessary to shield the beam or mantelpiece to protect it.
In order for the fire to operate correctly there must be an air gap
behind the appliance of at least 40mm, but be aware that this
distance will need to be greater in some cases to meet Building
Regulation requirements.
The appliance should be installed on a floor with adequate load-
bearing capacity. If an existing construction does not meet this
requirement then please take suitable measures to achieve this. (e.g.
load distributing plate.)
CONNECTIONS TO FLUES
There are several ways of connecting the stove to the flue. These are
illustrated in figures 9 to 12.
If a top flue connection (as shown in Fig. 11) or the vertical rear flue
connector (shown in Fig. 12) are used, then the chimney may be
swept through the appliance.
11
charnwood
I S L A N D
IIIII