User Instructions

HEALTH AND SAFET Y PRECAUTIONS
Please take care when installing the stove that the requirements of
the Health and Safety at Work Act 1974 are met.
Some types of fire cement are caustic and should not be allowed to
come into contact with the skin. In case of contact wash with plenty
of water.
If there is a possibility of disturbing any asbestos in the course of
installation then please use appropriate protective equipment.
There must not be an extractor fan fitted in the same room as the
stove as this can cause the appliance to emit fumes into the room.
There must be an adequate air supply into the room in which the
appliance is installed to provide combustion air. The combustion air
supply must be via a permanently open vent. The requirement for
minimum free area is partly dependent on the design air permeability
of the house. In older properties the air permeability will be above
5.0m³/(h.m²), but in some modern properties it may be less. The
vent must be positioned such that it is not liable to blockage.
Minimium areas are given in the following table:
This stove is capable of intermittent operation, and is not suitable for
use in a shared flue system.
A fixed ducted air supply may be used as an alternative to the
traditional method of using a permanent open vent into a room to
supply air for combustion.
External air supply kits are available please contact Charnwood for
more information.
In addition to these instructions the requirements of BS.8303 and
BSEN 15287-1:2007 must be fulfilled. Local Authority Bylaws and
Building Regulations, including those referring to national and
European Standards, regarding the installation of Solid Fuel burning
appliances, flues and chimneys must also be observed.
UNPACKING THE STOVE
The stove arrives bolted and shrink-wrapped to its pallet. There must
be adequate facilities for unloading and manoeuvring into position.
The wrapping is first removed, then the stove released from the
pallet by either removing the single bolt (C-4) or 4 pallet bolts(C-5 to
C-8) using a 10mm spanner. The pallet brackets can now be removed
from the stove by tilting it and using a 13mm spanner to remove the
bolts. These 4 bolts are required for levelling or fixing on the Store
Stand or High legs. The Stove may now be moved to its final
position. The pallet is intended to be cut up and used for kindling fuel.
CO ALARMS
Building regulations require that whenever a new or replacement
fixed solid fuel or wood/biomass appliance is installed in a dwelling a
carbon monoxide alarm must be fitted in the same room as the
appliance. Further guidance on the installation of the carbon
monoxide alarm is available in BS EN 50292:2002 and from the
alarm manufacturer's instructions. Provision of an alarm must not be
considered a substitute for either installing the appliance correctly or
ensuring regular servicing and maintenance of the appliance and
chimney system.
SPECIFICATION
The outputs in the table are based on a 45 minute re-fuelling cycle
burning seasoned hardwood logs. All tests are carried out in
accordance with BSEN 13240.
9
®
INSTALLATION INSTRUCTIONS
Air
Permeability
m³/(h.m²)
Minimum Vent Area cm²(in²)
C-Four
C-Five
C-Six
C-Seven
C-Eight
> 5.0
No
Requirement
No
Requirement
9.4 (1.5)
11 (1.76)
16.5 (2.6)
<5.0
27.5 (4.3)
27.5 (4.3)
36.9(5.7)
38.5 (6.0)
44 (6.8)
Specification
C-Five
C-Six
C-Seven
C-Eight
Nominal Heat
Output
kW (BTU/hr)
5.0
(17,000)
5.9
(20,100)
7.1
(25,900)
8.3
(28,300)
Stove Weight kg
(Packed)
96
96
115
119
Flue
Temperature °C
247
243
280
316
Minimum
Flue Draught
12Pa
12Pa
12Pa
12Pa
Flue gas Mass
Flow g/s
4.2
5.1
7.3
6.3
Hearth
Temperature °C
69.9
88.1
55.4
53.4
Minimum
distance from
combustibles
mm
500 side
400 rear
500 side
500 rear
500 side
500 rear
600 side
650 rear
*The results will be marginally reduced if the grate kit is fitted