User Manual

19
PUSH
BUTTON
DOOR SENSOR
(SUPERVISED)
DOOR STRIKE
MAGLOCK
DOOR SENSOR
(NON-SUPERVISED)
OR
EOL (End of Line) Resistor
(1k ohm)
PROXIMITY
SENSOR
For DC Power:
Install a 1N4005
diode or equivalent
Use 18-22 AWG
Model MG1300
Power for Maglock
(Not Provided)
DO NOT use the power
supply for the controller
For AC Power:
Install a Siemens S10K30MOV
(Metal Oxide Varistor) or equivalent
Use 18-22 AWG
For AC Power:
Install a Siemens S10K30MOV
(Metal Oxide Varistor) or
equivalent
For DC Power:
Install a 1N4005
diode or equivalent
Power for Door Strike
(Not Provided)
Model HES(R) 1006CLB(R)
REQUEST TO EXIT
GROUND
SUPERVISED
NORMALLY OPEN
COMMON
NORMALLY CLOSED
NORMALLY OPEN
COMMON
+
NORMALLY OPEN
COMMON
+
NORMALLY CLOSED
COMMON
OR
OR
REQUEST TO EXIT
SUPERVISED (DOOR STATUS)
PRIMARY RELAY
ALARM BYPASS
NORMALLY OPEN
COMMON
AUXILIARY RELAY
OR
DOOR 1, 2, 3, or 4
NOTE: The length of the unshielded
wires should be kept to a minimum to
avoid electrical noise.
RED LED - brown
GREEN LED - orange
DATA 1 - white
DATA 0 - green
SHIELD - shield
GROUND - black
12Vdc - red
not used - yellow
not used - blue
not used - purple
PROXIMITY READER
OR
KEYPAD
OR
WEIGAND
RFID RECEIVER
with wiegand output
Power for RFID RECEIVER
(Not Provided)
DO NOT use the power
supply for the controller
LIGHT
LOAD
LINE
NEUTRAL
NOTE: DO NOT
run high voltage
power within
the ACXL
enclosure.
Isolation
Relay
Low
Voltage
Power
Supply
NOTE: For KPR2000
keypad, wire the pink and
black (ground) wires together.
Door Access
Disconnect power BEFORE making electrical connections. Below is an example of a wiring setup for door access. Door access can be
wired to Door 1, 2, 3, or 4 on the Door Boards.
PRE-INSTALL NETWORK PROGRAMMINGINSTALL ACCESS CONTROLINTRODUCTION