Gate Access (Wireless)
The CAPXM can communicate wirelessly to LiftMaster
®
UL325 gate operators to send open commands, monitor gate position, and send
email notifications if an error occurs in the operator (email notifications are configured in myQ
®
Business™). Up to 4 gate operators can
be paired with the CAPXM - one for each primary and auxiliary relay. If using dual gates, program the CAPXM to the primary operator.
NOTE: Use of this feature requires the optional Passport antenna kit.
1 Enter Admin Mode
Flip switch #1 to the ON position to
enter Admin Mode.
NOTE: For new
installations press
the login button
without entering
information in the
Admin Username
and Admin
Password fields.
2 Select Outputs and Relay
Select the Outputs tab. Then select the
desired relay on the left-hand side (1
through 4).
3 Press LEARN button on gate
operator
Press and release the LEARN button
on the primary operator. The green
XMITTER LED will light. NOTE: The
operator will time out of programming
mode after 180 seconds.
4 Press LEARN button on gate
operator again
Press and release the LEARN button
again on the primary operator. The
yellow NETWORK LED will light.
5 Select LEARN on display
Select the LEARN button on the
display and the Learn button will go
from blue to red. The gate operator
and the CAPXM will beep once and the
NETWORK LED on the gate operator
will turn off indicating programming is
successful.
NOTE: 4 beeps/blinks indicate you
are not programming to the primary
operator. Reattempt programming
from the other operator.
DIAGNOSTICS
DIAGNOSTICS
6 Validate
Validate functionality by selecting Test
Relay on the CAPXM display.
Admin
Visit myQBusiness.com for more information on how to set up doors for wireless linking.