Specifications

Figure 16: 6-Pin Modular Jack Pinout Details
Commissioning Devices on the MS/TP Bus
Commission the devices on the local and remote MS/TP buses using the CCT software. Refer to CCT Help
(LIT-12011147) for information on commissioning an MS/TP bus application.
Applications and device configurations are downloaded to the hardware from the CCT computer using the Wireless
Commissioning Converter or through the NAE, NCE, or Open Data Server (ODS) from the Metasys UI. Refer to the
BACnet® Controller Integration with NAE/NCE Technical Bulletin (LIT-1201531) for more information.
Hardware points can be auto discovered from the online UI of the NAE, the Application and Data Server (ADS), the
Extended Application and Data Server (ADX), or the Open Data Server (ODS).
Peer-to-Peer Communication
Peer-to-peer communication allows non-supervisory engines on a bus to communicate system data with each other
directly, bypassing the supervisory engines (NAE/NCE) on the bus.
39MS/TP Communications Bus Technical Bulletin