5. System status levels
The UPS module shall be provided with a control/indicator panel. The panel shall be on the
front of the UPS module. Controls, meters, alarms and indicators for operation of the UPS
module shall be on this panel.
2.2.5.1 Graphic Operator Terminal Liquid Crystal Display (LCD):
A. The LCD touch screen interfaces with the UPS Module Control and main processor
board to pro vide menu-driven operator instructions and UPS Module operation
details. The LCD indicates system operation, operational guidance, measurement
data, set up data and alarm messages and logs. All metering shall be digitally
displayed on the LCD having an accuracy of 1% or better .
B. The touch screen area is composed of four MENU sheets: MAIN, MEASUREMENT,
OPERATION, and STATUS. Each MENU sheet has a name t ab at the top and the
four name tabs form an overlap index at the top of the screen area. Touching the
name tab of any of the MENU sheets at this index will make that specific MENU be
displayed. Each MENU sheet displays specific in formation and includes touch icons
that perform MENU related functions.
1. MAIN MENU Sheet: The MAIN MENU indicates power flo w and measured
values. The LCD panel allows the user to verify the status and operation of the
UPS Module components by the mimic display. The followin g information is
available on the MAIN MENU Sheet:
a. Converter operation
b. Battery operation
c. Load on inverter
d. Load on bypass
e. Typical measurement values of Input, Bypass, Battery and Output
f. Alarm/Fault messages
2. MEASUREMENT MENU Sheet: The MEASUREMENT MENU indicates
measured values. The following information is available on the MEASUREMENT
MENU Sheet:
Display information:
a. Input V olt age and Frequency
b. By pass Voltage and Frequency
c. Battery Voltage and Charging/Discharging Current
d. Output V oltage, Frequency and Current
e. Output active po wer
f. Output power factor
3. OPERATION MENU Sheet: The OPERATION MENU Sheet prompts the user to
select specific performance and UPS setting data. (re mote or local start & stop
operation, date & time adjustment, battery test etc.)
4. STAT US MENU Sheet: The STATUS MENU Sheet indicates event and
alarm/fault information and battery discharge records. A maximum of 50 events
can be displayed. The following alarm/status information shall be available as a
minimum: