Specifications

U-ENS00011_99AtypSMSSpec_Rev2.doc
12
Copyright © 2008, Mitsubishi Electric Power Products, Inc.
U-ENS00011 Rev2 12/9/08
wrap-around cont actor shall derive po wer from an upstream bypass feed contactor
internal to the UPS module. The wra p-around contactor shall be electrically connected in
parallel to the static switch and shall, at the same time as the static switch, be energized
and upon closure maintain the critical load feed from the bypass source. T he static
sw itch shall only be utilized for the tim e needed to energize the wrap-around contactor
therefore increasing reliability. The bypass circuit shall be capable of supplying the
UPS rated load current and also provide fault clearing current capabilities. The UPS
system logic shall employ sensing which shall cause the static switch to energize within
150 microseconds therefore pro viding an uninterrupted transfer to the bypass source
when any of the following limitations are exceeded:
1. Inverter output undervolt age or overvoltage.
2. Overloads beyond the capability of the inverter.
3. DC circuit undervoltage or overvoltage.
4. Final voltage of system battery is reached (bypass source present and available).
5. System failure (e.g.: logic fail, fuse blo wn, etc.).
B. Automatic Re-transfers
In the event that the critical load must be transferred to the bypass source due to an
overload, the UPS system logic shall monitor the overload condition and, upon the
overload being cleared, perform an automatic re-transfer back to the in verter output.
The UPS system logic shall only allow a re-transfer to occur three times within a five
minute period. Re-transfers shall be inhibited on the fourth transfer due to the likelihood
of a recurring problem at the UPS load distribution. All retransfers will be inhibited if the
inverter and static bypass line are not synchronized.
C. Manual T ransfers
The UPS shall be capable of transferring the critical load to/from the bypass source via
the front control panel. If performing manual retransfers to inverter or automatic
retransfers, the UPS system logic shall force the inverter output voltage to match the
bypass input voltage and then parallel the inverter and bypass sources providin g a
make-before-break transition allowin g a controlled walk-in of load current to the inverter.
Manual transfers will be inhibited if the inverter and static bypass line are not
synchronized.
D. Static Switch
The static switch shall be a high speed transfer device comprised of naturally
commutated Thyristors. During manual transfers the static switch is not required. The
static switch shall not use fuses for protection.
2.2.5 Operation/Display Panel
The control panel shall employ the use of a touch screen interface which allows lock-out of
all UPS control function for security (The Emerge ncy Power Off function shall not be
locked out). The operator interface shall provide the following:
1. UPS start-up procedure
2. UPS shutdown procedure
3. Emergency Power Off (EPO)
4. Audible alarm silence