Service manual

Configuration
2-8 Revision L 96022
StorageTek Protected
Setting the Warning and Shutdown Temperatures
Use this menu to protect media. Refer to the documentation from the media
manufacturer to determine what temperatures to set. The high temperature is
automatically recorded.
You are not required to set the warning and shutdown temperatures. The display still will
report LLC card fan, drive fan, and power supply failures.
Access the Hardware Monitor Menu and complete the required fields as shown
in the following table. For more information about this menu, see
“Viewing the Status of the Hardware Monitor” on page 2-12.
Resetting the Library
CAUTION:
Possible equipment damage: Use a wooden pencil (never a screwdriver
or other electrical conductor) to press the
RESET button to prevent
damaging the button or the LLC card.
To activate the configuration information in the library’s memory, you must reset the
library. After entering all your configuration information, use a wooden pencil to press
the
RESET button on the rear of the library, or press the inline power switches to the O
position, then to the — position.
Resetting the library by pressing the
RESET button will make the library configuration
active, but it will not cause the library to perform an audit. If an audit is required because
cartridges have been moved, you must open and shut the door, or press the inline power
switches to the O position, then to the — position.
After you set some of the configuration values described in this chapter, you reset the
library using the operator panel. When you press the
MENU button to exit the
Table 2-4. Hardware Monitor Menu
Data Field Explanation
High Temp: The display shows the highest Celsius temperature. If desired, press
SELECT to clear the temperature.
Warn Temp: Use the arrows to set the desired Celsius temperature. When the
library reaches the temperature, the SERVICE REQUIRED
indicator blinks.
Shutdown
Temp:
Use the arrows to set the desired Celsius temperature. When the
library reaches the temperature, the SERVICE REQUIRED
indicator remains lit and no additional move requests are accepted.
Note: The value for the shutdown temperature must be at least
2ºC higher than the value for the warning temperature.