Specification

Underground Feeder Cable
UF-B
Cirtuf
®
Underground
Feeder Cable
©2010, Cerro Wire LLC
All Rights Reserved
MADE IN THE USA
90°C Insulation
600 Volts
Sunlight-Resistant
Jacket
APPLICATIONS
For use underground as a feeder or branch circuit cable where provided with
overcurrent protection of the rated ampacity as speci󰘰ed by the NEC
®
. Direct burial
in the earth is permitted. May be installed as interior wiring in wet, dry, or corrosive
locations as speci󰘰ed by the NEC
®
May be installed as nonmetallic-sheathed cable as
speci󰘰ed in NEC
®
Section 340.10(4). May be installed in locations with temperatures up
to 90°C but with the ampacity limited to that of 60°C conductors.
CONDUCTORS
• Solid conductors: Soft, uncoated copper per ASTM-B3
• Stranded conductors: Uncoated copper per ASTM-B3 and ASTM-B8
CONDUCTOR INSULATION AND JACKET
• Color-coded PVC (polyvinyl chloride), rated 90°C dry
• Insulated conductors also jacketed with clear nylon (polyamide)
GROUNDING CONDUCTOR
• Soft, uncoated copper per ASTM-B3
ASSEMBLY
Insulated conductors are laid parallel with a bare grounding conductor
JACKET
A gray, sunlight-resistant PVC (polyvinyl chloride) is applied directly over and around
the insulated and bare conductors
INDUSTRY STANDARDS
• UL 83 (insulated conductors) File No. E15119
UL 493 Thermoplastic-Insulated Underground Feeder and Branch Circuit Cables -
File No. E26403
• ASTM-B3
• ASTM-B8
• Federal Speci󰘰cation A-A-59544
• NFPA70: National Electrical Code
®
• RoHS Compliant
SURFACE PRINT
• Sample: TYPE UF-B SUN-RES SIZE 12-2 W/G CIRTUF-A 600V (UL)