Owner's Manual
MMB-2 AUX Power
1. AUX power is available on TB5 terminals 9-12
2. All wiring must be in accordance with Article 760 of NEC
or local building codes.
3. AUX power is power limited to NFPA 70/NEC 760.
4. Electrical Ratings: 18-31 VDC, 1A max.
MMB-2 Notification Appliance Circuits
(TB5, 1-4 and TB5, 5-8)
1. These notification appliance circuits are for alarm
notification appliances only (NFPA 72 Local). For
Municipal tie (NFPA 72, Chapter 4 ) or Leased Line
(NFPA 72 Chapter 4), use model CSM-4.
2. All wiring must be in accordance with Article 760 of NEC
or local building codes.
3. Both notification appliance circuits are power limited to
NFPA 70/NEC 760.
4. Electrical Ratings:
Supervisory 18-31 VDC, 12mA max
Alarm 18-31 VDC, 1.5A max.
5. End of Line Device: EOL 2.2K, 1/2W (P/N 140-820380)
6. Line Resistance: Not to exceed 3 ohms max
MXL Compatible Analog/Intelligent
Devices
Model Description
Installation
Instructions
CZM-1 Conventional Zone Module 315-090725
ILI-1/1H/1A/1AH Intelligent Ion Detectors 315-092724
ILP-1/IPLT-1 Intelligent Photo Detectors 315-092594
ILT-1 Intelligent Heat Detectors 315-093336
ILI-1B/1BH Intelligent Ion High Vel. 315-093234
ILP-2
FirePrintâ„¢ Application
Specific Detection
315-095028
MSI-10B/20B Intelligent Manual Station 315-093329
MS-MI
Intelligent Metal Manual
Station
315-092169
TRI-B6/B6D/B6R
Intelligent Monitor Module
(single/dual and with relay)
315-093315
TRI-B6M
Intelligent Mini-Monitoring
Module
315-094547
ICP Intelligent Control Point 315-092471
LIM-1 Line Isolator Module 315-092135
firealarmresources.com