Owner's Manual

Typical Wiring Diagram
NOTES:
1.1. If shielded cable is being used, the following wiring
details should be adhered to::
A. If the device is connected to a ground electrical box, the
shields should be wired through and not connected to
ground. The earth ground terminal of the device should be
tied to the electrical box.
B. If shielded cable is used in grounded metallic raceway, tie
the shield through and tie the earth ground terminal to the
electrical box/raceway.
C. If the device is connected to a non-grounded electrical
box tie the shields to the earth ground terminal.
D. If shielded cable is used without raceway or in non-
metallic raceway tie the shields to the earth ground
terminal.
firealarmresources.com