Owner's Manual

ELECTRICAL CONNECTIONS FOR RELEASING
SERVICE (per NFPA 12A, NFPA 13, and NFPA 2001)
1. Set switches S3 and S4 and jumpers G1 and G2 as
indicated in Table 2.
2. Set all positions of switch S2 to OFF (OPEN).
3. All wiring must be in accordance with Article 760 of NEC
or local building codes.
4. Both circuits are not power limited.
5. Solenoids are supervised for opens only.
6. Electrical Ratings:
Solenoids: 24 VDC, 16.8 watts max,
700mA max
Supervisory Current:12mA max
Alarm Current: 800mA max
Wire Resistance: 3 ohms max
7. Compatible Solenoids:
NFPA 13:
ASCO Model T8210A107
ASCO Model R8210A107
ASCO Model 8210A107
SKINNER Model LV2LBX25
NFPA 12A:
PYRO P/N 500-982631
PYRO P/N 500-286652
PYRO P/N 500-083377
PYRO P/N 500-086929
NFPA 2001:
KIDDE FENWAL Model 486500-1
8. No End of Line Device used.
Notes:
1. Polarity shown in supervisory state.
2. Maximum line resistance 3 ohms.
3. Releasing zones are not power limited to NFPA 70
per NEC 760.
4. Releasing solenoids are supervised for opens only.
CSM-4 Loop Wiring for use as Releasing Service
(per NFPA 12A, NFPA 13, and NFPA 2001)
Table 2 — Setting the Mode Of Operation
(Using S3, S4 and G1, G2)
For Circuit 1
S3
Position
G1
Audibles [NAC] (NFPA 72 Local)
Municpal Tie (NFPA 72)
Leased Line
(NFPA 72 Remote Station)
Releasing Service (NFPA 12A)**
Releasing Service (NFPA13)**
Releasing Service (NFPA 2001)**
Illegal (Results in a trouble
on the CSM-4)
1
1
2
1
1
1
2
Not Cut
Cut
Not Cut
Cut
Cut
Cut
Cut
For Circuit 2
S4
Position
G2
Audibles [NAC] (NFPA 72 Local)
Municpal Tie (NFPA 72)
Leased Line
(NFPA 72 Remote Station)
Releasing Service (NFPA 12A)**
Releasing Service (NFPA13)**
Releasing Service (NFPA 2001)**
Illegal (Results in a trouble
on the CSM-4)
1
1
2
1
1
1
2
Not Cut
Cut
Not Cut
Cut
Cut
Cut
Cut
Note: If circuit 1 or circuit 2 is not used for leased line trouble,
dipswitches SW1 or SW2 must be off (open).
Table 3 — Setting the Degrade Trouble Modes on S2
For Circuit 1 SW4 SW3
OFF (no default activation)
CONTINUOUS (active on default alarm)
1 SEC ON, 1 SEC OFF (infinite repeat)
DO NOT USE
Off (Open)
Off (Open)
On (Closed)
On (Closed)
Off (Open)
On (Closed)
Off (Open)
On (Closed)
For Circuit 2 SW6 SW5
OFF (no default activation)
CONTINUOUS (active on default alarm)
1 SEC ON, 1 SEC OFF (infinite repeat)
DO NOT USE
Off (Open)
Off (Open)
On (Closed)
On (Closed)
Off (Open)
On (Closed)
Off (Open)
On (Closed)
Note: When circuits are used for leased line supervisory, the alarm
default modes must be set to OFF (open)
Table 4 — Setting the Degrade Alarm Modes on S2
** Canada Only: Do not cut jumpers G1 and G2 for NFPA 12A, NFPA 13 and NFPA 2001
For Circuit 1 SW1
Leased Line Trouble
No Trouble Activation
On (Closed)
Off (Open)
For Circuit 2 SW2
Leased Line Trouble
No Trouble Activation
On (Closed)
Off (Open)