Instruction Manual

Eng ineer and Arc hitec t Spec ific a tionsEng ineer and Arc hitec t Spec ific a tions
AE-30U
For Style “Y” systems, a notification appliance circuit for operating 120 Vac or 24 Vdc polarized audible alarm devices shall
be provided by a Cerberus Pyrotronics Audible Alarm Class “B” Module, Model AE-30U. This module shall be system
interconnected by a ten-pin plug and harness assembly and shall be operable with the main control panel.
Upon receipt of a high-going DC actuating signal, the solid state circuitry shall supply operating power for AC bells or AC
horns. For DC devices it shall power vibrating DC bells, DC horns or strobes. The maximum output current shall be limited
to 1.5 amperes. The audible devices shall require a four wire fused, supervised circuit.
The module shall contain a yellow LED indicator lamp to indicate an open or shorted alarm line when the system is in the
normal condition. The LED shall be lamp tested from the main control panel.
The Model AE-30U shall be placement supervised and shall be Underwriters Laboratories, Inc. listed.
CP-35
CP-35
(See Note 2)
3 Ohms max Total Line
Resistance of Notification
Appliance Circuit
Connecting Wires
End of Line Device
(See Note 1)
Polarized Notification
Appliances (See Note 3)
Actuation
Input
Input Power
(See Note 1)
Style Y (Class B)
Connected
Polarized
Notification Appli-
ances
Polarity Shown in
Supervisory
Condition:
SUPV 24VDC, 5mA
Alarm 24VDC or
120VAC,
1.5 Max
Note:
Refer to the BI-35
Installation Instructions, P/
N 315-086257, for detailed
wiring information when
using the AE-30U in
conjunction with the BI-35
module.
Notes:
1. When emergency power is provided using charger/transfer module, Model BC-35, 24 VDC
notification appliances must be used with EOL device, Model EL-31. When BC-35 is not
used, 120 VAC notification appliances may be employed by use of AC program plug, Model
JP-A, in P2 of CP-35 and Model EL-32 EOL device, or by use of 24 VDC notification
appliances with DC program plug, Model JP-D, in P2 and Model EL-31 EOL device.
2. Notification appliance circuits may be activated from the silenceable system alarm output
signal, terminal 36 of CP-35, or from the non-silenceable system alarm output signal,
terminal 42 of CP-35. When other alarm signals such as coding or time delay/limit are
required, see individual module connection diagrams.
3. Use only the compatible polarized notification appliances in the following table.
4. To use power limited wiring to NFPA 70, NEC Article 760, the notification appliance circuits
(terminals 3 and 4) must use the PLM-35 module. Refer to Instructions P/N 315-093495.
TABLE 1
COMPATIBLE NOTIFICATION APPLIANCES
Strobes
Electronic
Horns
1-Tone
with strobe
Electro-Mech.
Horn/Strobes
Electronic
S.W./Chime
Chimes/
Strobes
S15-FS
S15-F
S15-FT
S15-ST
S15-S
S17-FS
S17-F
S17-S
S17-FT
S17-ST
S75-FS
S75-F
S75-S
S75-FT
S75-ST
S110-FS
S110-F
S110-S
S110-FT
S110-ST
EH-S15-F
EH-S15-S
EH-S15-C
EH-S17-F
EH-S17-S
EH-S17-C
EH-S75-F
EH-S75-S
EH-S110-F
EH-S110-S
HN-S15-F
HN-S15-S
HN-S15-C
HNH-S15-F
HNH-S15-S
HNH-S15-C
HN-S17-F
HN-S17-S
HN-S17-C
HNH-S17-F
HNH-S17-S
HNH-S17-C
HN-S75-F
HN-S75-S
HNH-S75-F
HNH-S75-S
HN-S110-F
HN-S110-S
HNH-S110-F
HNH-S110-S
EW-S15-F
EW-S15-S
EW-S15-C
EW-S17-F
EW-S17-S
EW-S17-C
EW-S75-F
EW-S75-S
EW-S110-F
EW-S110-S
EC-S15-F
EC-S15-S
EC-S15-C
EC-S17-F
EC-S17-S
EC-S17-C
EC-S75-F
EC-S75-S
EC-S110-F
EC-S110-S
Vibrating
Bells
Horns/Horn Strobes
3-Tone 8-Tone
Electro-
Mech. Horns
Electronic
Horns
1-Tone
BT-F
BE-F
BS-F
BF-F
BT-LC
BE-LC
BS-LC
BF-LC
MC-F
MC-S
MC-C
MC-S15-F
MC-S15-S
MC-S15-C
MC-S17-F
MC-S17-S
MC-S17-C
MC-S75-F
MC-S75-S
MC-S110-F
MC-S110-S
MT-F
MT-S
MT-C
MT-S15-F
MT-S15-S
MT-S15-C
MT-S17-F
MT-S17-S
MT-S17-C
MT-S75-F
MT-S75-S
MT-S110-F
MT-S110-S
HN-F
HN-S
HN-C
HNH-F
HNH-S
HNH-C
HNH-EP
HN-EP
EH-F
EH-S
EH-C
Tri-Horn
TTH
Chimes Electronic Slow Whoop
EC-F
EC-S
EC-C
CH-F
EW-F
EW-S
EW-C
firealarmresources.com