Spec Sheet
731.9
[28.8]
637.6
[25.1]
LEFT SIDE VIEW
642
[25.3]
76.2 [3.0]
PEA GRAVEL
MINIMUM
TRANSFER
SWITCH
8KW - 17KW
(IF SUPPLIED)
TRANSFER
SWITCH
20KW
(IF SUPPLIED)
1218
[47.9]
FRONT VIEW
1226
[48.3]
H2
H1
W1
W2
H2
H1
W1
W2
Standby Generator - 8 kW & 12 kW
TRANSFER SWITCH & PRIORITY LOAD CENTER Model 05534 (8 kW) Model 05536 (12 kW)
No. of Poles 2 2
Current Rating (amps) 100 100
Voltage Rating (VAC) 250 250
Utility Voltage Monitor (fixed)
-Pick-up
-Dropout
75%
65%
75%
65%
Return to Utility approx. 15 sec. approx. 15 sec.
Exerciser weekly for 12 minutes Standard Standard
UL Listed Standard Standard
Dimensions (H” x W” x D”) 26.5 x 12.5 x 7 26.5 x 12.5 x 7
Total of Pre-wired Circuits
No. 15A 120V
No. 20A 120V
No. 20A 240V
No. 30A 240V
No. 40A 240V
8
5
1
-
1
-
12
5
3
-
1
1
Circuit Breaker Protected
Available RMS Symmetrical
Fault Current @ 250 Volts 10,000 10,000
GENERAC POWER SYSTEMS, INC. • P.O. BOX 297 • WHITEWATER, WI 53190
WEBSITE: www.centuriongenerators.com
Bulletin 0176810SBY / Printed in U.S.A. 04.08 © 2008 Generac Power Systems, Inc. All rights reserved.All specifications are subject to change without notice.
731.9
[28.8]
637.6
[25.1]
LEFT SIDE VIEW
642
[25.3]
76.2 [3.0]
PEA GRAVEL
MINIMUM
TRANSFER
SWITCH
8KW - 17KW
(IF SUPPLIED)
TRANSFER
SWITCH
20KW
(IF SUPPLIED)
1218
[47.9]
FRONT VIEW
1226
[48.3]
H2
H1
W1
W2
H2
H1
W1
W2
Transfer Switch Features
• Electrically operated,
mechanically-held contacts for
fast, positive connections.
• Rated for all classes of load,
100% equipment rated, both
inductive and resistive.
• 2 pole, 250 VAC contactors.
• 160 millisecond transfer time.
• Dual coil design.
• Main contacts are silver plated
or silver alloy to resist welding
and sticking.
• NEMA 1 (indoor rated)
enclosure is standard on the 100
amp switch.
Design and specifications subject to change without notice. Dimensions shown are approximate. Contact your Generac dealer for certified drawings. DO NOT USE THESE DIMENSIONS FOR INSTALLATION PURPOSES.
Mechanical Dimensions (in inches)
Current
Rating
No. of
Poles
Height Width Depth
H1 H2 W1 W2
7100 UL Listed 2 26.5 29.25 8.14 12.5
Terminal Wire Ranges
ATS Rated Amps Switch Terminal Neutral Lug/Stud Ground Lug
100A 2-Pole UL 1 x 1/0-12 1 x 3/8-16 Stud 1 x 2/0-14