Specifications
40 
Note:  Bolts used to secure the FTB type heating element assembly in 
CEMLINE Electric Water Heaters and Boilers are rated as either Grade 
A or Grade 5. Grade A bolts have no marking on the head. Grade 5 
bolts are designated by three (3) slash marks on the head (///). 
a.  Lubricate the bolt threads and the nut faces with a suitable 
lubricant. 
b.  Insert the bolts through the flanges, then start the nuts. 
c.  Number all bolts so that torquing requirements can be followed. 
Note:  Appendix B contains drawings depicting the typical flange 
configurations (number of bolts, location, tightening sequence, etc.)  
for CEMLINE Electric Water Heaters and Boilers. Reference the 
applicable drawing for the unit being serviced. 
d.  Apply torque in twenty percent (20% [1/5]) steps of required final 
torque, loading all bolts at each step before proceeding to the next 
step. The following tables list ANSI approved target torques for 
both Grade A and Grade 5 bolts. The correct target torque can be 
determined by the nominal pipe size, number and grade of bolts 
used to secure the flange, and the size of the bolt used. 
Garlock Bolt Torque Values 
Grade A Bolts 
  .062" Ring Gaskets  ANSI - 150
#
 Flanges 
Nominal Pipe Size 
(IN) 
Number of Bolts 
Size of Bolts 
(IN) 
Grade A 
Target Torque 
(FT - LBS) 
3"  4  5/8"  96 
4"  8  5/8"  96 
5"  8  3/4"  160 
6"  8  3/4"  160 
8"  8  3/4"  160 
10"  12  7/8"  184 
12"  12  7/8"  184 
14"  12  1"  250 
16"  16  1"  250 