Specifications

31
The auxiliary high temperature limit thermostat will also "trip" when the water
temperature surpasses the temperature set on the thermostat. However, the
auxiliary high temperature limit thermostat will reset automatically when the water
temperature drops below the set temperature.
Replacement
If any of the thermostats are found to be malfunctioning and need to be replaced,
follow the procedures detailed below.
1. Follow Steps 1 through 5 of the shutdown procedure (page 19) to take the
unit off-line before attempting to replace the thermostat(s).
t The combination of electricity and water can pose a very dangerous
situation. Assure that all power has been shut off / disconnected and
locked out in an approved manner, before attempting any installation or
maintenance procedures.
2. After assuring that the power has been turned off, the pressure bled from
the tank, the water drained, and the unit has cooled, unlock and open the
electric control cabinet door.
3. Locate the thermostat to be replaced and tag the wires attached to the
thermostat to assure proper reconnection after the new thermostat has been
installed.
4. Disconnect the wires from the thermostat terminals.
5. Trace the capillary tube leading from the thermostat to the tank. It may be
necessary to move a small portion of the fiberglass insulation to gain access
to the location on the tank where the temperature probe is mounted. The
capillary tube connects the thermostat body to the temperature probe
mounted within the tank.
6. The temperature probe is mounted to the tank via a compression fitting.
The body of the compression fitting can be difficult to remove from the
tank. To facilitate removal, cut the capillary tube with a pair of diagonals
or wire cutters close enough to the compression fitting body to allow a six
(6) point socket to be used to remove it from the tank.
Note: Do not remove the compression fitting cap nut. This could allow the
temperature probe to become free and possibly fall into the tank.
7. Using the correct size six (6) point socket, remove the body of the
compression fitting from the tank. The remainder of the capillary tube, still