Specifications
19 
  If all pilot lights are illuminated, the system has adequate water and is functioning 
within the high temperature limit. 
8.  After approximately thirty (30) minutes of operation, shut off and lock out the 
power and feel each wire connection and fuse clip for excessive temperature. If 
any connection or clip is found to be excessively hot, check to assure the integrity 
of the connection. All connections must be tight for proper operation. 
9.  Close and lock the door to the electric control cabinet. 
10.  Turn on the power supply. 
11.  After the unit has reached operating temperature, reinspect all joints for signs of 
leakage. In addition, check the pressure and temperature gauges to verify that the 
water temperature and pressure are within design specifications. 
12.  The unit is now ready for normal operation. 
Shutdown Procedures 
1.  Turn off the electric power supply at the unit and at its source, and lock out the 
power supply in an approved manner before proceeding. 
t  The combination of electricity and water can pose a very dangerous situation. 
Assure that all power has been shut off / disconnected and locked out in an 
appropriate manner, before attempting any installation or maintenance procedures. 
2.  Turn off the cold water inlet and hot / boiler water outlet shutoff valves. 
3.  Relieve the pressure within the unit by means of the relief valve and vent / drain 
system. 
4.  After the system has cooled, drain the unit by opening the tank drain valve and 
holding the pressure relief valve in the open position. This will prevent the 
formation of a vacuum and help to the increase the drainage flow. 
5.  Proceed with the required maintenance or repairs. 
6.  After performing the required maintenance or repairs, return the unit to operation 
by following the startup procedures detailed on page 17. 
Daily Operation - Electric Water Heaters and Water Boilers 
Daily operation of CEMLINE Electric Water Heaters and Boilers is totally automated. 
However, it is recommended that approximately twice a day the unit is checked to assure 