Specifications

www.whisperkool.com | Page 17
DRAIN LINE PUMP SYSTEM
1. Drain pan lls with water which ows into reservoir. Intake hose between reservoir and pump is empty (lled with 
air).
2. Raising water lifts oat, activating pump, which self primes by drawing water up from reservoir. During this period 
the pump is operating hot and dry and will click loudly. Once the air in the intake hose has been purged, water 
entering the pump cools and lubricates it so that the clicking noise becomes a low hum. Water ows through the 
pump and out of the discharge hose.
3. Water level in the reservoir has now receded enough to lower the oat, deactivating the pump. However, the 
weight of the water in the discharge hose plus atmospheric pressure at the drain pan outlet forces the water 
remaining in the intake hose to continue owing out through the pump until the reservoir, intake hose, pump and 
discharge hose are completely empty, at which point the siphoning stops.
4. As the evaporator produces more condensate, the drain pan again lls up with water which ows into the reservoir. 
Since the intake hose is lled with air again, the cycle repeats itself.
RESULT: EVERY TIME THE PUMP 
RUNS HOT AND DRY, IT SUSTAINS 
A SMALL AMOUNT OF DAMAGE 
WHICH CAUSES PREMATURE WEAR.
THE NEXT TIME THE PUMP STARTS 
UP DRY, IT MAY RUN FOR 11 
SECONDS BEFORE IT COOLS DOWN 
THE NEXT TIME 12 SECONDS 
AND SO ON. ALSO WHILE THIS IS 
OCCURRING, THE PUMP IS CLICKING 
LOUDLY. THIS IS ACCEPTABLE 
DURING THE INITIAL START UP 
PHASE, BUT NOT ACCEPTABLE 
DURING SUBSEQUENT OPERATIONS 
OF THE PUMP.
WHEN YOU CONSIDER THAT 
THIS WILL OCCUR A NUMBER 
OF TIMES EVERY DAY OF THE 
COOLING SEASON IT IS EASY 
TO SEE THAT THE DAMAGE WILL 
RAPIDLY ACCUMULATE. IF THE 
PUMP IS ALLOWED OPERATE IN 
THIS CONDITION REPEATEDLY, THE 
NOISY PERIOD WILL GET LONGER 
AND LONGER OVER THE COOLING 
SEASON UNTIL THE CUSTOMER 
COMPLAINS OR THE PUMP 
EVENTUALLY FAILS.
THIS CAN EASILY BE AVOIDED 
BY INSTALLING THE DISCHARGE 
HOSING CORRECTLY WITH AN 
ANTI-SIPHON DEVICE WHICH WILL 
EQUALIZE THE ATMOSPHERIC 
PRESSURE AND ELIMINATE THE 
SIPHONING.
INCORRECT: Failure to follow correct Discharge Hose installation will damage pump.
4
3
1
2
DRAIN PAN
DRAIN PAN
DRAIN PANDRAIN PAN
PUMP
PUMP
PUMPPUMP
BREATHER TUBE
BREATHER TUBE
BREATHER TUBEBREATHER TUBE
RESERVOIR
RESERVOIR
RESERVOIRRESERVOIR
ATMOSPHERE
PRESSURE