Specifications

CellarMate Manual Page 34
Unit Operates but the Power Switch Light is Not On
Possible Cause Solution
Bulb is burned out Replace bulb
Unit is Leaking Water
Possible Cause Solution
Trap plugged Clean trap
Condensate pan plugged Remove blockage and clean
Unit not level Level with shims
Unit is Running Properly, but the Sound of Unit is Objectionable
Possible Cause Solution
Noise is from air flow Redirect air flow
Add baffles
Add insulated ductwork
Noise is from unit Add sound baffle between unit and occupied
space
High Pressure Switch in the Refrigeration System Switch Shuts off Unit
Possible Cause Solution
The head pressure is above 275
psi
Restricted air flow through the condenser caused
by an obstruction blocking the air flow in the
ductwork or grille
Dust covering the filter
Contact a refrigeration technician