Specifications

CellarMate Manual Page 30
Unit Does Not Start Up
Power Switch Light is Off
Possible Cause Solution
Switch not on Turn on switch
No power to outlet Check circuit breaker and wiring
Unit not plugged in Plug in the unit
Power Switch Light is On and the Thermostat Light is OFF
Possible Cause Solution
No power to thermostat Check wiring for loose, broken, or frayed
connections.
Check transformer for 24v output to thermostat
Power Switch Light is ON and the Thermostat Light is OFF
Possible Cause Solution
Thermostat is not setup
properly
Check thermostat setup in the guide
Press fan ON switch to check evaporator fan,
only
Compressor not operating High pressure switch open (button up)
Condenser air flow is blocked Remove blockage
Clean filter and coil (if needed)
HP switch is open Reset HP switch (push button in)
High Pressure Switch Has Shut the Unit Down
Possible Cause Solution
Head pressure in unit is too
high because an obstruction is
restricting air flow through the
condenser
Remove the obstruction in the duct or grille or
clean the filter. Restart the unit using the high
pressure switch near the compressor (a cylindrical
device piped into the refrigeration system with
two wires and a red button on the top) and push in
the button until it locks into position again. Push
the rocker switch to restart the unit