Troubleshooting
IMPORTANT
This section is intended as a diagnostic aid, only. For detailed repair or parts
replacement procedures, contact a qualified service company. Check the
following table before calling a service technician.
Start Up
POSSIBLE CAUSE SOLUTION
Loose, improper, or defective
thermostat or humidistat
wiring
Check power and thermostat or humidistat
wiring.
Incorrect thermostat or
humidistat (optional) settings
Check the thermostat and optional humidistat
setup for the application. Read the thermostat
troubleshooting guidelines in the Thermostat
Installation and Operating Guide.
Changed settings on the
thermostat
The internal timer did not complete the timed
delay. Follow the manufacturer’s instructions to
override the timer.
Blockage of the evaporator or
condenser air flow. If the air
flow becomes blocked, the
manual reset high limit switch
opens and shuts the unit off.
Turn the rocker switch to OFF
Check for obstruction of the air flow
Remove the obstruction
Inspect the air filter for dirt and dust
Clean or replace the filter
Unit shuts off Locate the high pressure switch near the
compressor (a cylindrical device piped into the
refrigeration system with two wires and a red
button on the top)
Push the button until it locks into place.
Push the rocker switch to restart the unit