Specifications
CellarMate Manual Page 18
Setting the Thermostat
Normal settings are between 54 and 58°F. If the unit is equipped with an optional heating
coil, enter a separate temperature setting to maintain the lower setting. To prevent the unit
from short cycling, the setting between heating and cooling cannot be closer than 2°F. The
built-in delay timer (20 minutes) will prevent the unit from switching from heating to cooling
too fast.
Regulating the Wine Cellar Temperature
Wine cellars have a temperature gradient of 5 to 10° between floor and ceiling. Change the
air flow patterns to raise or lower the temperature in different zones.
To maintain the same temperature throughout the wine cellar, set the thermostat to FAN so
the supply fans run continuously while the unit is cooling, as opposed to AUTO.
To switch from continuous to automatic mode, press the FAN button on the thermostat.
To switch back to automatic mode, press the FAN button again.
Changing the Air Flow Pattern
The CellarMate is equipped with single-direction grilles. Rotate the grilles 180° to change
the direction of the air flow.
When using multiple-supply ductwork, balance the air flow between the ductwork. If too
much air flows through one duct and not enough air flows through the other duct, install a
damper or other restriction device into the duct with too much air. This will force more air to
flow from the other duct.