Unit installation

HARBOR POINT WALL SPLIT DUCTLESS SYSTEMS
PRE INSTALLATION
Determine the best location for mounting
the indoor unit, it must be located a mini-
mum of 4 ft (6 ft or more recomended) from
the floor and no less than 6 from ceiling.
CONTROLS AND COMPONENTS
Units are supplied with a wireless remote
control, which communicates with the unit
microprocessor control. The return air
temperature sensor mounted in the in-
door unit provides input to the control for
system operation.
Pay attention to the air circulation in the
room, 9,000 & 12,000 Btuh units throw air
15ft, 18,000 & 24,000 Btuh units throw air
25ft, ensure no obstacles to airflow exist.
Several modes of operation are available
to the end user depending on the type of
comfort required. All unit operating func-
tions are controlled via the remote con-
trol. Refer to “System Operation” section
of this manual.
Locate the indoor and outdoor units as close
together as possible, maximum line set run
and lift MUST NOT BE EXCEEDED. Deter-
mine how the interconnect piping, wiring
and condensate hose are to be run.
OPTIONAL CONTROLS AND
COMPONENTS
Lift
Low Ambient Control:
Please consult the factory for availability of
approved method of low ambient cooling
operation.
Condensate Pump:
It is recommended to use the supplied
condensate drain hose in a gravity fed
method whenever possible. If this can
not be done then a field installed pump
that is external to the evaporator would
be required.
Ensure that all panels can be removed for
service as required.
Certification:
All Harbor Point Systems are certified by
UL under UL Standard 1995. Per-
formance is varified by CSA under ARI
210/240 test standard.
5
Unit
Max
Line
Set
Run
Max
Vertical
HF-25/HF-35
50
Feet
17
Feet
HF-51/HF-70
50
Feet
17
Feet
HFR-25/HFR-35
50
Feet
17
Feet
HFR-51/HFR-70
50
Feet
17
Feet