Unit installation
HARBOR POINT WALL SPLIT DUCTLESS SYSTEMS
Start the 
indoor
 unit,  
cooling
mode
is
only
allowed
when
 the outside ambient 
temperature 
is
above
 60°  F  to prevent 
damage
 to the 
compressor
. Unit 
has
a
3 
minute time 
delay
 before the 
compressor 
start 
up
 operation. 
Note: If interconnect is less then 25 feet 
a small amount of refrigerant may need 
to be reclaimed to achieve the proper 
charge for optimal operation. We 
recommends fine tuning using the 
“Superheat” method. 
FIELD CHARGING 
For proper superheat readings, a standard 
low-side refrigerant gauge and an accurate 
thermometer  is  needed.  A  mercury  or 
stem-type  thermometer  is  not  adequate 
for suction-line temperatures. We recom- 
mend electric thermocouple thermometers 
(available at most refrigeration wholesal- 
ers);  however  an  accurate  remote-bulb 
thermometer can be used. When measur- 
ing the line temperature, be sure the ther- 
mometer  is  securely  attached  to  assure 
accurate measurements. The chart below 
gives superheat values at various outdoor 
temperatures. Allow at least 5 minutes run- 
ning time between charge adjustments for 
the unit to stabilize. 
The use of the superheat method is highly 
recommended for field charging or check- 
ing  the  existing  refrigerant  charge  in  a 
system that is in the cooling cycle. Because 
each  installation  is  different  in  terms  of 
indoor air flow, refrigerant line length, etc.., 
the  factory  charge  may  not  be  correct 
for every application. To assure the best 
performance from the air-conditioner, the 
refrigerant charge should be checked and 
adjusted, if need be, on each installation. 
Note: Refrigerant superheat is the tem- 
perature above the suction pressure at 
its saturation temperature. 
SUPERHEA
T
 CHAR
GING
 CHAR
T
Chart based on 
360
 to 
400
 CFM/ton indoor air flow and 
50%
 relative humidity 
Use
 on 
systems
 that cool with capillary or piston 
50
Indoor dry bulb temperature 
45
40
90
35
30
25
20
15
10
5
55
60
65
70
75
80
85
90
95
100
105
OUTDOOR TEMPERATURE °F 
110
115
Note: If operating superheat is more than 5° F above the chart value, add refrigerant. If 
below the chart value remove refrigerant. If below the limit line, remove refrigerant. 
15 
SUPERHEAT CHARGING CHART 
SUPERHEAT °F 
95
°F 
85
80
75
70










