Unit installation
Install the line set on the 
indoor unit stubs. 
HARBOR POINT WALL SPLIT DUCTLESS SYSTEMS
Service port 
Gas line service valve 
Line set connections 
under the GRAY 
caps. 
Outdoor 
Unit 
Liquid line service valve 
9,000/12,000 shown 
18,000/24,000  has additional 
  liquid line port 
remove line 
set cover 
Indoor Unit 
10 
Refrigerant Line Set Piping 
Interconnecting    line    set    between    the 
outdoor unit and the indoor unit, must have 
both  refrigerant   lines   insulated   as   the 
expansion  device  is  located  in  the  outdoor 
unit. 
Gently  bend the line  set  stubs from the 
in-   door   unit   to   the   desired   location. 
Using  2  x  10”/12”  Crescent  wrenches 
remove  the  flare  nuts  from  the  indoor 
unit line stubs. 
The  indoor   unit   is   filled   with   a   dry 
gas,  check for  release  of  this to  ensure 
that  no  leaks  are  present.  Use  a  small 
amount  of  vacuum  pump oil on  the  male 
flare threads to ease installation. 
Connect   the   line set   to  the  stubs.  
Using the  2 wrenches,  1 on the  male 
and  1  on the  female  tighten  the  flare 
nuts. Run the line  set  to the  outdoor  
unit,    avoid    tight  bends and  kinking 
the lines. 
If  line  set  length  is  in  excess  of  that  
re- quired, cut line set and re-flare or 
coil  ex-  cess  vertically  to  facilitate  oil 
return to the compressor. 