Phau Ntawv Qhia
FSI-751Plug-inIntelligentIonizationSensor
InstallationandMaintenanceInstructions
GENERALDESCRIPTION
ModelFSI-751isanintelligentsensorthatusesastate-of-the-artionizationsensingchamber.Thissensorisdesignedtoprovideopenareaprotectionand
isintendedforusewithcompatiblecontrolpanelsonly.
TwoLEDsoneachsensorlighttoprovidealocal,visiblesensorindication.RemoteLEDannunciatorcapabilityisavailableasanoptionalaccessory(Part
No.RA400Z).
Notierpanelsofferdifferentfeaturesetsacrossdifferentmodels.Asaresult,certainfeaturesoftheFSI-751maybeavailableonsomecontrolpanels,but
notonothers.ThesensorwillsupporteitherFlashScan™orCLIP(ClassicLoopInterfaceProtocol)mode.ThepossiblefeaturesavailableintheFSI-751,
ifsupportedbythecontrolunitinclude:
1. ThepanelcontrolstheLEDoperationonthesensor.OperationalmodesareREDblink,REDcontinuous,GREENblink,andoff.
2. TheremoteoutputmaybesynchronizedtotheLEDoperationorcontrolledindependentoftheLEDs.
PleaserefertotheoperationmanualfortheULlistedcontrolunitforspecicoperationoftheFSI-751.
SPECIFICATIONS
OperatingVoltageRange: 15to32VDC
Max.Avg.StandbyCurrent: 300µA@24VDC(onecommunicationevery5sec.withLEDblinkenabled)
Max.AlarmCurrent(LEDon): 6.5mA@24VDC
OperatingHumidityRange: 10%to93%RelativeHumidity,noncondensing
OperatingTemperatureRange 0°to49°C(32°to120°F)
Height: 1.7inches(43mm)installedinB710LPBase
Diameter: 6.1inches(155mm)installedinB710LPBase
4.1inches(104mm)installedinB501Base
Weight: 3.6oz.(102g)
WARNING
Disconnectlooppowerbeforeinstallingsensors.
Beforeinstallingthesensor,pleaserefertotheSystemSmokeDetectorApplicationGuide.Thismanualincludesdetailedinformationonsensorspacing,
placement,zoning,andspecialapplications.CopiesofthismanualareavailablefromNotier.
1. SensorInstallation
a. Settheaddressonthesensorperjobdrawings.
NOTE:Somepanelssupportextendedaddressing.Inordertoset
thesensoraboveaddress99oncompatiblesystems,carefullyremovethestop
ontheupperrotaryswitchwiththumborngerasshowninFigure2.
b. Insertthesensorintothebaseandrotateitclockwiseuntilitdropsintoplace.
c. Continuetorotatethesensoruntilitlocksintothebase.
CAUTION
Dustcoversareaneffectivewaytolimittheentryofdustintosmokedetectorsensingchambers.However,theymaynotcompletelypreventairborne
dustparticlesfromenteringthedetector.Therefore,Notierrecommendstheremovalofdetectorsbeforebeginningconstructionorotherdustproducing
activity.
Besuretoremovedustcoversfromanysensorsthatwereleftinplaceduringconstructionaspartofreturningthesystemtose
2.Tamper-Resistance
ModelFSI-751includesatamper-resistantcapabilitythatpreventsitsremovalfromthebracketwithouttheuseofatool.Refertothebasemanualfor
detailsonmakinguseofthiscapability.
3.Afterallsensorshavebeeninstalled,applypowertothesystem.
4. SeeFigure3.Testthesensorbypositioningatestmagnet(M02-04)againstthesensorplasticinthemagnettestarea.Thealarmlevelshouldberec-
ognizedatthepanelandtheLEDcontrolledbycommunicationcommandfromthepanel.
N500-57-00 1 I56-1249-04R
Notier12ClintonvilleRd,Northford,CT06472-1653,(203)484-7161
3
2
1
3
2
1
3
2
1
+
-
-
+
U.L.LISTEDCOMPATIBLE
CONTROLPANEL
CLASSAOPTIONALWIRING
REMOTEANNUNCIATOR
+ -
CAUTION:Donotloopwireunderterminal1or2.
Breakwireruntoprovidesupervisionofconnections.
WIRINGGUIDE
Refertotheinstallationinstructionsfortheplug-inbase
beingused.AsindicatedinFigure1,terminalsforpower,
ground,andtheoptionalRA400ZRemoteAnnunciator
areincludedinthebase.BaseModelsB710LP(shown
inFigure1)andB501areelectricallyidentical.
NOTE:Allwiringmustconformtoallapplicablecodes,
ordinances,regulationsandtothecontrolpanelspec-
ications.
NOTE:Verifythatallsensorbasesareinstalledandthat
polarityofthewiringiscorrectateachbase.
Figure1.
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
9
BREAKAWAYSTOP
Figure2.