N500-53-00 1 ฀฀฀฀฀ I56-1230-06R
฀฀฀฀฀฀฀฀Notifier,฀12฀Clintonville฀Rd,฀Northford,฀CT฀06472,฀(203)฀484-7161฀
FSP-751฀and฀FSP-751T฀Intelligent฀Photoelectronic฀Smoke฀Sensors
Installation฀and฀Maintenance฀Instructions
This฀sensor฀must฀be฀installed฀in฀compliance฀with฀the฀control฀panel฀system฀installation฀manual.฀The฀installation฀must฀meet฀the฀requirements฀of฀the฀Authority฀
Having฀Jurisdiction฀(AHJ).฀Sensors฀offer฀maximum฀performance฀when฀installed฀in฀compliance฀with฀the฀National฀Fire฀Protection฀Association฀(NFPA);฀see฀NFPA
72.฀
GENERAL฀DESCRIPTION
Model฀FSP-751฀and฀FSP-751T฀are฀intelligent฀sensors฀that฀combine฀a฀state-of-the-art฀photoelectronic฀sensing฀chamber฀with฀communications.฀The฀FSP-751T
adds฀thermal฀sensors฀that฀will฀alarm฀at฀a฀fixed฀temperature฀of฀135°F.฀These฀sensors฀are฀designed฀to฀provide฀open฀area฀protection฀and฀are฀intended฀for฀use฀with฀
compatible฀control฀panels฀only.
Two฀LEDs฀on฀each฀sensor฀light฀to฀provide฀a฀local,฀visible฀sensor฀indication.฀Remote฀LED฀annunciator฀capability฀is฀available฀as฀an฀optional฀accessory฀(Part฀No.฀
RA400Z).
Notifier฀panels฀offer฀different฀features฀sets฀across฀different฀models.฀As฀a฀result,฀certain฀features฀of฀the฀FSP-751฀or฀FSP-751T฀may฀be฀available฀on฀some฀control฀
panels,฀but฀not฀on฀others.฀The฀possible฀features฀available฀in฀the฀FSP-751฀and฀FSP-751T,฀if฀supported฀by฀the฀control฀unit฀are:
1. The฀panel฀controls฀the฀LED฀operation฀on฀the฀sensor.฀Operational฀modes฀are฀RED฀blink,฀RED฀continuous,฀GREEN฀blink,฀and฀off.
2. The฀remote฀output฀may฀be฀synchronized฀to฀the฀LED฀operation฀or฀controlled฀independent฀of฀the฀LEDs.
Please฀refer฀to฀the฀operation฀manual฀for฀the฀UL฀listed฀control฀unit฀for฀specific฀operation฀of฀the฀FSP-751฀and฀FSP-751T.
SPECIFICATIONS
Operating฀Voltage฀Range: 15฀to฀32฀VDC
Standby฀Current: 300µA@฀24฀VDC฀(onecommunication฀every฀5฀
seconds฀with฀LED฀blink฀enabled)
Max.฀฀Alarm฀Current฀(LED฀on):฀฀฀฀฀฀฀฀ 6.5฀mA฀@฀24฀VDC
Operating฀Humidity฀Range: 10%฀to฀93%฀Relative฀Humidity,฀noncondensing
Operating฀Temperature฀Range:฀฀฀฀฀฀฀ 0°฀to฀49°C฀(32°฀to฀120°F);฀FSP-751
Operating฀Temperature฀Range:฀฀฀฀฀฀฀ 0°฀to฀38°C฀(32°฀to฀100°F);฀FSP-751T
Height: 1.7฀inches฀(43฀mm)฀installed฀in฀B710LP฀Base
Diameter: 6.1฀inches฀(155฀mm)฀installed฀in฀B710LP฀Base
4.1฀inches฀(104฀mm)฀installed฀in฀B501฀Base
Weight: 3.6฀oz.฀(102฀g)
SPACING
Notifier฀recommends฀spacing฀sensors฀in฀compliance฀with฀NFPA72.฀In฀low฀air฀
flow฀applications฀with฀smooth฀ceilings,฀space฀sensors฀30฀feet฀apart.฀For฀specific฀
information฀regarding฀sensor฀spacing,฀placement,฀and฀special฀applications,฀refer฀
to฀NFPA฀72฀or฀Notifier’s฀System฀Smoke฀Detector฀Application฀Guide,฀available฀at฀
no฀charge฀from฀Notifier.
Duct฀Applications:฀FSP-751฀and฀FSP-751T฀are฀listed฀for฀use฀in฀ducts.
See฀Duct฀Applications฀Guide฀A05-1004฀for฀details฀on฀pendant฀mount฀applications.
NOTE:฀฀These฀products฀are฀not฀listed฀for฀use฀inside฀duct฀smoke฀detectors.
WIRING฀INSTRUCTIONS
All฀wiring฀must฀be฀installed฀in฀compliance฀with฀the฀National฀Electrical฀Code,฀applicable฀
local฀codes,฀and฀any฀special฀requirements฀of฀the฀Authority฀Having฀Jurisdiction.
Proper฀wire฀gauges฀should฀be฀used.฀The฀installation฀wires฀should฀be฀color-coded฀to฀
limit฀wiring฀mistakes฀and฀ease฀system฀troubleshooting.฀Improper฀connections฀will฀prevent฀
a฀system฀from฀respondingproperly฀in฀the฀event฀of฀a฀fire.
Disconnect฀power฀from฀the฀communication฀line฀before฀installing฀sensors.
All฀wiring฀must฀conform฀to฀applicable฀local฀codes,฀ordinances,฀and฀regulations.
1. Wire฀the฀sensor฀base฀(supplied฀separately)฀per฀the฀wiring฀diagram฀(Figure฀1).
2. Set฀the฀desired฀address฀on฀the฀sensor฀address฀switches.
NOTE:Some฀panels฀support฀extended฀addressing.฀In฀order฀to฀set฀the฀sensor฀above฀address฀99฀on฀compatible
฀systems,฀carefully฀remove฀the฀stop฀on฀the฀upper฀rotary฀switch฀with฀thumb฀as฀shown฀in฀Figure฀2.
3. Install฀the฀sensor฀into฀the฀sensor฀base.฀Push฀the฀sensor฀into฀the฀base฀while฀turning฀it฀clockwise฀to฀secure฀it฀in฀place.
4. After฀all฀sensors฀have฀been฀installed,฀apply฀power฀to฀the฀control฀unit฀and฀activate฀the฀communication฀line.
5. Test฀the฀sensor(s)฀as฀described฀in฀the฀TESTING฀section฀of฀this฀manual.
TESTING
Before฀testing,฀notify฀the฀proper฀authorities฀that฀the฀system฀is฀undergoing฀maintenance,฀and฀will฀temporarily฀be฀out฀of฀
service.฀Disable฀the฀system฀to฀prevent฀unwanted฀alarms.฀฀฀฀฀฀
All฀sensors฀must฀be฀tested฀after฀installation฀and฀periodically฀thereafter.฀Testing฀methods฀must฀satisfy฀the฀Authority฀Having฀
Jurisdiction฀(AHJ).฀Sensors฀offer฀maximum฀performance฀when฀tested฀and฀maintained฀in฀compliance฀with฀NFPA฀72.฀The฀sen-
sor฀can฀be฀tested฀in฀the฀following฀ways:
3
2
1
3
2
1
+
+
OPTIONAL฀RETURN฀LOOP
REMOTE฀ANNUNCIATOR
+
CAUTION
Dust฀ covers฀ provide฀ limited฀ protection฀ against฀ airborne฀ dust฀ particles฀ during฀ shipping.฀ Dust฀ covers฀ must฀ be฀
removed฀before฀the฀sensors฀can฀sense฀smoke.฀Remove฀sensors฀prior฀to฀heavy฀remodeling฀or฀construction.
Figure฀1.฀Wiring฀Diagram
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
9
Sperre,฀Ausbruchstelle
Figure฀2.฀Rotary฀Address฀Switches
LED฀STATUS
INDICATORS
TEST
MAGNET
PAINTED
SURFACE
PAINTED
SURFACE
MAGNET฀TEST
MARKER
D
O
N
O
T
P
A
I
N
T
TEST
MAGNET
Figure฀3.
Caution:฀Do฀Not฀Loop฀Wire฀Under฀Terminal฀1฀or฀2.
Break฀Wire฀Run฀To฀Provide฀Supervision฀of฀Connections.

Summary of content (2 pages)