Specifications
ACI/Frangkiser Hutchens Architects 4-07058
Liberty "North" Second High School
Liberty Public School District #53
Building Construction Bid Set
FOOD SERVICE EQUIPMENT 11400-41
opening and door. Factory-wire heater wires to j-box at door
section.
a. If non-heat controlled antisweat heater(s) are used at
entry door, the total door rail, glass and frame heater
shall draw no more than 7.1 watts per square foot of door
opening (for freezers).
b. If heat controlled antisweat heater(s) are used at entry
door, and the total door rail, glass, and frame heater power
draw is more than 7.1 watts per square foot of door opening
(for freezers), the antisweat heat controls shall reduce
the energy use of the antisweat heater in a quantity
corresponding to the relative humidity in the air outside
the door or to the condensation on the inner glass pane.
3. When a concrete wear surface is shown poured atop walk-in box
floor panels, provide heated threshold flush in finished
floor at entry door and extended height door frame(s) to allow
for concrete wear surface and threshold.
4. Provide with spring loaded, positively closing door hinges.
5. Provide 14 gauge stainless sill plate with non-skid
stripping, extend onto kitchen floor.
6. Provide each door section with exterior, flush mounted,
4-1/2" diameter N.S.F. listed chrome plated dial thermometer.
7. Provide each door with cylinder operation dead bolt lock with
reinforced installation in door and panel, safety release on
inside. All door keyed alike. Provide (5) keys.
8. On exposed-to-view exterior and interior of walk-in doors,
provide 36"H. wainscots constructed of .188 - 6061-T6 mill
finish aluminum tread plate and 3
rd
door hinge, Mechanically
secure tread plate to door and seal thereto. Provide door
with 3
rd
hinge.
9. Provide doors into non-refrigerated spaces with an interior
mounted thermo-plastic, insulating, slatted curtain.
10. Provide a window in the door. Minimum 14" x 14" window.
Freezer door window shall be of triple pane glass with either
heat-reflective treated glass or gas fill with heated frame.
Window shall be field replaceable. Window centered at 60"
aff.
J. Interior lighting;
1. On the exterior of the door section, adjacent to the door,