Specifications
ACI/Frangkiser Hutchens Architects 4-07058
Liberty "North" Second High School
Liberty Public School District #53
Building Construction Bid Set
FOOD SERVICE EQUIPMENT 11400-120
using R-404A. Install compressor, refrigerant piping and
refrigerant as specified, hereinafter. See Refrigeration
Requirements sub section of this specification section.
Equivalent manufacturers must provide equipment of similar
dimensional size, and comparable construction and same or
higher BTU refrigeration capacities with similar utility
requirements to the refrigeration system on which this
specification is based. Use of equivalent manufacturers
equipment shall not require major changes to the plan, the
equipments location or to electrical service designated within
the contract documents. Any minor changes required are the
responsibility of the provider to coordinate with other trades
and all costs associated with changes shall be covered by the
provider. Listed Equivalent manufacturers are responsible for
verifying they comply with these requirements before submitting
a bid.
l. By alternate, provide pre-fitted remote refrigeration system
for remote installation as located on drawings, including all
standard parts, refrigeration specialties, factory sized
refrigeration lines, air cooled condensing units, with
weather-proof covers and low ambient kit/winter controls
using head pressure control valves and other items necessary
for a complete and properly operating system. Hang
evaporators with double nutted nylon bolts. Provide (5) year
compressor warranty.
2. By alternate, provide Refrigerator Item No. T1 with Kolpak
Industries Model PR-154-M, 10775 BTU/Hr. pre-fitted R404A
remote Semi-hermetic refrigeration system with 1.5
horsepower condensing unit and matched evaporator coil for
refrigerator to operate at 35
o
F. Alternate manufacturers
include, Penn, Norlake, Master-Bilt
3. Weather proof covers shall include hail screens.
B. Condensing unit shall be set on the roof top above the walk-in
location, set on curbs provided by other trades.
C. Extend evaporator condensate drain as shown. Extend drain
lines with copper tubing having minimum diameter of 5/8" radius
per manufacturers recommendations. Run lines as shown with
minimum slope of 1/4" per foot.
D. It is the intention of this specification for a complete