Specifications
ACI/Frangkiser Hutchens Architects 4-07058
Liberty "North" Second High School
Liberty Public School District #53
Building Construction Bid Set
FOOD SERVICE EQUIPMENT 11400-117
insulation. Provide 90
o
angled sections at all corners. Food
service contractor shall provide penetrations thru insulated
cabinet exterior & is responsible for sealing them.
1. Provide verification, as required by the code authority, that
the box complies with the code requirements for use of foam
plastic insulation in buildings and structures. Cost of the
verification to be borne by the provider of the walk-in box.
2. Sections are fitted together with mating tongue and groove
panel perimeters having thermoplastic hooded gaskets at
interior and exterior edges. Provide non-conductive strip,
in all exterior sections, at joints where partitions butt.
Sections fasten together with quick acting cam, "Posi-Loks".
Access ports to cam-locks shall be on interior. Spacing
between fasteners on vertical joint shall not exceed 45", at
vertical to horizontal joints and horizontal joint, 23".
Cover all cam fasteners wrench holes, with thermoplastic
press-fit caps.
3. On exposed-to-view exterior of walk-in box panels, provide
a 36"H. wainscot of mechanically secured and sealed thereto.
4. Ceiling color, White.
H. Hinged Door shall be 36" x 78". Construct door exterior with
22 ga. stainless steel, interior of same material as interior
walls. Door shall be infitting flush type and with insulation
same thickness and material as wall sections. Fiberglass
Reinforced Plastic door perimeter, jamb and threshold. Heavy
duty cast alloy door handle and hinges with powder coat finish.
Three (3) positive action self-closing hinges with stainless
steel pin and nylon rising cam bearing. Door handle with key
lock and inside 1/4 turn safety release handle. Provide
thermoplastic gasket with magnetic core at door top and both
sides and adjustable sweep gasket at door bottom edge. Provide
heater wires around perimeter of door opening and door.
Factory-wire heater wires to J-box at door section. Hinge doors
as shown on plan.
1. Provide door with automatic door closer that firmly close
door to within 1 inch of full closure. Door shall self close.
Hinge doors as shown.
2. Provide anti-sweat heater wires around perimeter of door
opening and door. Factory-wire heater wires to j-box at door