E.2 Installation Conditions/auxiliaries
These characteristics are mentioned as a reminder, and are given in the
CDA 7 5330 Site Preparation Guide.
Electrical environment:
• 220 V - 20 A single phase, output by an electric box (International).
• Maximum distance from box 6 feet (2 m)
• 20 A (International) breaker
• Maximum consumption 1.547 kVA
Physical dimensions and size:
• Height: 46 inches (116.9 cm)
• Width: 21 inches (53.3 cm)
• Depth: 36 inches (91.4 cm)
• Floor area: 15.75 sq.ft. (1.4 square meters)
• Service width in front and behind: 36 inches (91.4 cm)
Heat dissipation:
5,174 BTU/hr in maximum configuration