Operating instructions

Preventive Maintenance Manual
110 Copyright © 2012 EVG
5.14 Water filter
Open the water filter and clean it. If there are any deposits in the sieve
check your cooling water quality. To find the location of the water filter
refer to the picture below.
5.15 Water Cooling/Glycol Mix
5.15.1 Cooling Water Quality:
Closed loop system filtered (100 micron filters); the cooling water must
be mechanically clean, optically clear, without deposits, to keep the
cooling circuit free from dirt and organic suspended matter. To avoid
corrosion damages, the following requirements for the cooling water
must be met:
5.15.2 Requirements:
Recommended is the mixing of inhibited Propylenglycol 30 - 50 % Vol.
in DI-Water (e.g.: Heat Transfer Fluid Dowcal 20 from DOW Chemical
Company)
pH value: 7 – 8.2
max. oxygen content: < 4mg/kg (ppm) - due to level of
Propylenglycol
5.16 Water Flow
The cooling water flow is also permanently checked by the software. If
the water is turned off, there must be an error message after some time.
317 of 370