User guide
10
FX5 TECHNICAL DATA FOR 60 HZ
ELECTRIC HEATERS
C US
Model
Note
Voltage
Nominal
Wattage
Phase
Max. Motor
Nameplate
Current
Heater
Wattage
Total
Current
Minimum
Circuit
Ampacity
Supply
Wire
Maximum
Fuse Size
Temperature
Rise
Core Kit
Part Number
Contactor
Part
Number
(V) (kW) (W) (A) (A) (AWG) (A) °F °C
FX5-208160-030 208 3.0 1 2.7 2700 14.4 18.0 12 20 19.0 10.5 12116 10557
FX5-208160-050 208 5.0 1 2.7 4700 24.0 30.0 10 30 31.6 17.6 12117 10557
FX5-208160-075 208 7.5 1 2.7 7200 36.1 45.1 6 50 27.9 15.5 12118 10557
FX5-208160-100 * 208 10.0 1 2.7 9690 48.1 60.1 4 70 37.2 20.7 12119 10558
FX5-208360-030 208 3.0 3 1.4 2700 8.3 10.4 14 15 11.2 6.2 12116 10557
FX5-208360-050 208 5.0 3 1.4 4700 13.9 17.4 12 20 18.6 10.3 12117 10557
FX5-208360-075 208 7.5 3 1.4 7200 20.8 26.0 10 30 27.9 15.5 12118 10557
FX5-208360-100 208 10.0 3 1.4 9700 27.8 34.8 8 35 37.2 20.7 12119 10557
FX5-208360-150 208 15 3 1.4 14400 41.6 52.0 6 60 27.1 15.1 12120 10557
FX5-240160-030 240 3.0 1 2.7 2700 12.5 15.6 12 20 19.0 10.5 12122 10557
FX5-240160-050 240 5.0 1 2.7 4700 20.8 26.0 10 30 31.6 17.6 12123 10557
FX5-240160-075 240 7.5 1 2.7 7200 31.3 39.1 8 40 27.9 15.5 12124 10557
FX5-240160-100 240 10.0 1 2.7 9700 41.7 52.1 6 60 37.2 20.7 12125 10557
FX5-240160-150 * 240 15.0 1 1.4 14400 62.5 78.1 2 80 27.1 15.1 12126 10558
FX5-240360-030 240 3.0 3 1.4 2700 7.2 9.0 14 15 19.0 10.5 12122 10557
FX5-240360-050 240 5.0 3 1.4 4700 12.0 15.0 14 15 31.6 17.6 12123 10557
FX5-240360-075 240 7.5 3 1.4 7200 18.0 22.5 10 25 27.9 15.5 12124 10557
FX5-240360-100 240 10.0 3 1.4 9700 24.1 30.1 8 35 37.2 20.7 12125 10557
FX5-240360-150 240 15.0 3 1.4 14400 36.1 45.1 6 50 27.1 15.1 12126 10557
FX5-240360-200 * 240 20.0 3 1.4 19400 48.1 60.1 4 70 36.1 20.1 12127 10558
FX5-480160-030 ° 480 3.0 1 1.3 2700 6.3 7.9 14 15 19.0 10.5 12129 10557
FX5-480160-050 ° 480 5.0 1 1.3 4700 10.4 13.0 14 15 31.6 17.6 12130 10557
FX5-480160-075 ° 480 7.5 1 1.3 7200 15.6 19.5 12 20 27.9 15.5 12131 10557
FX5-480160-100 ° 480 10.0 1 1.3 9700 20.8 26.0 10 30 37.2 20.7 12132 10557
FX5-480160-150 ° 480 15.0 1 1.3 14400 31.3 39.1 8 40 27.1 15.1 12133 10557
FX5-480160-200 ° 480 20.0 1 1.3 19400 41.7 52.1 6 60 36.1 20.1 12134 10557
FX5-480360-030 480 3.0 3 0.7 2700 3.6 4.5 14 15 19.0 10.5 12129 10557
FX5-480360-050 480 5.0 3 0.7 4700 6.0 7.5 14 15 31.6 17.6 12130 10557
FX5-480360-075 480 7.5 3 0.7 7200 9.0 11.3 14 15 27.9 15.5 12131 10557
FX5-480360-100 480 10.0 3 0.7 9700 12.0 15.0 14 15 37.2 20.7 12134 10557
FX5-480360-150 480 15.0 3 0.7 14400 18.0 22.5 10 25 27.1 15.1 12133 10557
FX5-480360-200 480 20.0 3 0.7 19400 24.1 30.1 8 35 36.1 20.1 12134 10557
FX5-480360-250 480 25.0 3 1.0 24200 30.1 37.6 8 40 22.0 12.2 12135 10557
FX5-480360-300 480 30.0 3 1.0 29200 36.1 45.1 6 50 26.4 14.6 12136 10557
FX5-480360-350 480 35.0 3 1.0 34200 42.1 52.6 6 60 30.7 17.1 12137 10557
FX5-600360-030 600 3.0 3 0.6 2700 2.9 3.6 14 15 19.0 10.5 12138 10557
FX5-600360-050 600 5.0 3 0.6 4700 4.8 6.0 14 15 31.6 17.6 12139 10557
FX5-600360-075 600 7.5 3 0.6 7200 7.2 9.0 14 15 27.9 15.5 12140 10557
FX5-600360-100 600 10.0 3 0.6 9700 9.6 12.0 14 15 18.1 20.7 12141 10557
FX5-600360-150 600 15.0 3 0.6 14400 14.4 18.0 12 20 27.1 15.1 12142 10557
FX5-600360-200 600 20.0 3 0.6 19400 19.2 24.0 10 25 36.1 20.1 12143 10557
FX5-600360-250 600 25.0 3 0.8 24200 24.1 30.1 8 35 45.2 25.1 12144 10557
FX5-600360-300 600 30.0 3 0.8 29200 28.9 36.1 8 40 26.4 14.6 12145 10557
FX5-600360-350 600 35.0 3 0.8 34200 33.7 42.1 8 45 30.7 17.1 12126 10557
NOTES:
* Exceeds the 48 Amp Curcuit limit of NEC 424-22. DS5 not available for these units.
° 480 - 1 phase units are certied Class I, Div. 1, Group D and Class II, Div. 1 Groups F & G.
1. Minimum conductor size for 86˚F (30˚C) ambient. Derate conductor for ambient temperature. Use minimum 194˚F (90˚C) insulation.
2. Heater is functioning normally if at rated voltage the amp draw is within 10% of the value in this table.
3. Operation at lower voltages will result in reduced heat output and amp draw
4. Add "T" to model number when adding a built-in thermostat
5. Add "D" to model number when adding a built-in disconnect switch
6. Add "P" to model number when adding a built-in pilot light
7. Add "S" to model number when adding a 3-way switch
8. Add "H" to model number for units with high "off" (deenergized) ambient temperatures
9. Add "U" to model number for units with continuous fan option.
10. Add "A" to model number for units with stainless steel cabinet.