Specifications
Castle Care-Tech Ltd. Engineering
Page 12 - 2 Chapter 12
To address these items, identify
the address coding switches,
and open the switches to add
up to the required address,
thus:
Switch
Address
1248
16
00
CCCC C
01 O
CCC C
02
C
O
CC C
03 O O
CC C
04
CC
O
CC
05 O
C
O
CC
06
C
OO
CC
07 OOO
CC
08
CCC
O
C
09 O
CC
O
C
10
C
O
C
O
C
11 O O
C
O
C
12
CC
OO
C
13 O
C
OO
C
14
C
OOO
C
15 OOOO
C
C
denotes switch closed,
O
denotes open.
B: PRE-POWER UP
CHECKS
Perform a final check before
powering up:
1: POWER SUPPLIES – must be
adequate for the
intended loading.
2: WIRING – must conform to
the specifications
shown in this manual.
3: CONNECTIONS – must be
correctly made, with no
loose ‘whiskers,’ etc.
When you are satisfied that
these are all correct, and that
all components (except
keypads) are correctly
addressed, proceed .…
C: POWERING UP
Power up initially on MAINS
only. An alarm will be
generated. Proceed to the
nearest Keypad, which will
display (from power up)
EURO KEYPAD
v.1.19 17/08/02
After 10 seconds, blanks,
then:
ADDRESS
[- -]
Key
00
and YES
LANGUAGE
English [00]
Press
A
to exit to normal
mode, and use default code
(
1234
) to silence the
alarm.
When the display shows
Call Engineer
Batt Fault 100
- and NOT before
–
connect the battery to the
End Station.
Additional keypads on the
system must all be addressed in
the same way, ensuring that no
address duplicates another
Keypad, Tag Reader, or Access
Control or Guard Tour point.