Specifications
4
Controller Models S-Series - 2/4/8 doors per controller ( CAS-2S/4S/8S )
Advanced - Series -12/16 doors per controller ( CAS-12S/16S )
Microprocessor Model Motorola 68HC11MCU
Operating Frequency S-Series: 8 MHz Advanced-Series: 12 MHz
Clock System Real-Time
EPROM / Flash S-Series 64K Bytes / 128K Bytes Advanced-Series 128K Bytes
R A M S-Series: 128K Bytes Advanced-Series: 1M Bytes
W atchdog 1 Internal and 1 External
Battery Back-Up for Memory 3.6V onboard rechargeable backup battery
Type of Storage System Used Static RAM
Operating Temperature Range 0-65”C
Baud Rate 9600 (Controller to reader) 2400 (PC to controller)
Stop Bits 1
Data Bits 8
Maximum Storage Capability S-Series: 5,000 cards user and 2,500 transactions
Advanced-Series : 5,000 cards user and 50,000 transactions
Input Voltage 12V DC
Input Voltage Tolerance 11V-13.8V DC
Rated Current Input 1 A
Number of Controllers Can Be Connected 16 or 32 Controllers (Depends on software version)
Number of Readers Can Be Connected S-Series: 4/8/16 readers (Depends on Controller Types)
Advanced-Series: 24/32 readers (Depends on Controller Types)
Type of Reader Technology -Contact-less Smart Card - W iegand 26 bits / Magnetic Signal
-Magnetic Stripe Track 2, ABA Format -Barcode 2/5 or 3/9 format
Type of Usage Stand-Alone (Reader to Controller)
Network-Operated (Reader to Controller to PC)
Communication Cable Used 1 Pair RS-485 from Reader to Controller for each bus
1 Pair RS-485 from Controller to PCI-Interface
Maximum Length of Communication 1 km (Cable Length)
Recommended Cable Type BELDEN Cable 24AWG Standard 1419 A
Housing Metal Casing with Tubular Cam Lock and coated with epoxy to prevent vandalism
Alarm Features S-Series: 4 digital inputs points & 1 relay output
Advanced-Series: 7 inputs point & 1 fire alarm
Alarm Arming/Disarming can be manually controlled or timer controlled
Timer S-Series: 100 Timer Sets with 3 Intervals
Advanced-Series: 256 Timer Sets with 3 Intervals
Time Zone S-Series: 100 user Time Zone (9 days/time zone)
Advanced-Series: 256 user Time Zone (9 days/time zone)
Support Multi-Door and Function available for S-Series and Advanced-Series
Anti-Pass Back
Holidays 2 types of 30 dates Progammable Holiday
Controller Programming Mode Security 3 Passwords: ( no access card needed)
*Technical Password - Diagnostics only
* User Password - Arming & Disarming only
* Master Password - Highest Privilege
Continuous Card Swiping Facility Function Available
When Door Is Open
Controller Display Unit 20 characters x 2 rows Liquid Crystal Display with back-light
Software Requirements Run on Window 95/98/NT/Millenium Edition or Compatible
(Recommended Configurations) Pentium II, 64MB RAM, 10GB Hard Disk and Display 800 x 600 resolution
Diagnostic Systems Built-In Diagnostics
Indications Sound Indication When Release Button Is Pushed, Door Left Open And Force Open
Programming Mode Menu Driven Programming & Software Programming
Log File Supporting Through Software Function Available
Auxiliary Relay Output 20 T ype Programmable Event ( Applicable for K-Series & Advanced-Series Only )
Interlocking Capability Function Available Between Any Pair of Door ( Applicable for N-Series Only )
Networking Door Access (S-Series)
Technical Specifications