Instruction Manual
INSTALLATION, OPERATION & MAINTENANCE MANUAL (IOM)     
IOM-PGR-1
03-14
I.  DESCRIPTION AND SCOPE
Model PGR-1 is a pressure reducing regulator used to control downstream (outlet or P2) pressure. Sizes are 
1/2" (DN15), 3/4" (DN20), 1" (DN25), 1-1/2" (DN40), 2" (DN50), 3" (DN80) and 4" (DN100). This model is applied 
primarily in gaseous service.
MODEL PGR-1
DIRECT-ACTING, PRESSURE LOADED
PRESSURE REDUCING REGULATOR
II. REFERENCES
  Refer to Technical Bulletin PGR-1-TB for tech ni cal 
specifi cations for this reg u la tor.
ABBREVIATIONS
 CW  –  Clockwise
 CCW  –  Counter Clockwise
 ITA  –  Inner Trim Assembly
III. INSTALLATION
SECTION III
SECTION II
SECTION I
1.  Regulator may be rotated around pipe axis 360 
degrees. For ease of maintenance, the rec om-
 mend ed position is with the cover dome (2) 
up wards.
2.  Provide space below, above, and around reg u la-
 tor for removal of parts during maintenance.
3.  Install block valves and pressure gauges to pro-
 vide means for adjustment, operation, bypass, 
or removal of the regulator. A pipeline strainer 
is recommended before inlet to remove typical 
pipe line debris from entering valve and damaging 
internal “soft goods”, primarily the dynamic seal.
 CAUTION
Installation of adequate overpressure pro tec tion is recom-
mended to pro tect the reg u la tor from overpressure and 
all down stream equip ment from damage in the event of 
regulator failure.
Model PGR-1 