Manual
INSTALLATION, OPERATION & MAINTENANCE MANUAL (IOM) 
IOM-DA5
11/13
I.  DESCRIPTION AND SCOPE
The Model DA5 is a spring operated back pressure regulator used to control upstream (inlet or P1) pressure. Sizes 
are 1/2" (DN15), 3/4" (DN20), 1" (DN25), 1 1/4" (DN32), 1 1/2" (DN40), 2" (DN50), 2 1/2" (DN65), 3" (DN80) and 
4" (DN100). With proper trim uti li za tion, the unit is suitable for liquid, gaseous, or steam service. The Model DA5 
is available in a more common “reverse” fl ow direction arrangement, that is balanced against outlet pressure varia-
tions, and a “standard” fl ow direction arrangement that is unbalanced. Refer to Technical Bulletin DA5-TB for design 
conditions and selection rec om men da tions. (NOTE: This product was formerly iden ti fi ed as a Model D5 or Type V; 
a Model DA5, D5 and Type V are one and the same product.)
MODEL DA5
DA5 - DIRECT-ACTING, SPRING LOADED
BACK PRESSURE REGULATOR
SECTION I
II. REFERENCES
  Refer to Technical Bulletin DA5-TB and DAG-TB for 
tech ni cal specifi cations of a Model DA5 regulator.
ABBREVIATIONS
CCW – Counter Clockwise
CW – Clockwise
ITA  –  Inner Trim Assembly
III. INSTALLATION
4.  Install block valves and pressure gauges to pro-
 vide means for adjustment, operation, bypass, 
or removal of the regulator. A pipeline strainer is 
recommended upstream of inlet port to remove 
typical pipe line debris from entering valve and 
damaging internal “soft goods”, primarily the dy-
namic side seal and V-TFE seat when applied.
5.  Upstream Sensing Installation Considerations  
– Internal or External Sensing:
a.  The regulator may be installed with internal 
or external sensing. Unless otherwise spec-
 i fi ed, the regulator is supplied by the factory 
with internal sensing. The regulator may be 
con vert ed in the fi eld to external sensing. (See 
Section VII maintenance, Part H – Converting 
Internal/External Sensing.
b.  Reference DAG-TB, Table DAG-12 for rec-
 om men da tions for applying external pressure 
sensing.
c.  For internal sensing, no external line is re-
 quired. For external sensing, use an external 
control line. The line is connected from the 
port 1/4" (DN8) NPT on the side of the body 
di a phragm fl ange (see following schematic) 
to a pressure tap upstream of the regulator.  
SECTION III
SECTION II
 CAUTION
For welded installations, all internal trim parts, seals and 
diaphragm(s) must be removed from reg u la tor body prior to 
welding into pipeline. The heat of fusion welding will dam-
 age non-metallic parts if not re moved. NOTE: This does 
not apply to units equipped with extended pipe nip ples.
1.  Install per direction of fl ow arrow indicated on body, 
or "IN" and "OUT" markings.
2.  Regulator may be rotated around pipe axis 360 
degrees. For ease of maintenance, the rec om -
mend ed position is with the spring chamber (4) 
upwards. In liquid service it is recommended that 
the spring cham ber be oriented down wards, and 
that a cus tom er supplied and installed vent valve 
be pro vid ed at the external sensing connection 
to bleed-off trapped gas/air under the diaphragm 
during initial startup.
3.  Provide space below, above, and around reg u la tor 
for removal of parts during maintenance.