User Manual
IOM-9540R
7
PART COLOR NO
NO. CODE COILS
light
gray
830-69-5-08002-00 7 -1/4
olive
green
830-69-5-08001-00 6 -3/4
light
yellow
830-69-5-08000-00 5 -3/4
Figure 8
Figure 9
CHARACTERIZATION CAM SELECTION & ORIENTATION
VS. CONTROL VALVE ACTION –
RANGER & PREMIER PRODUCTS
Figure 7
Input Product Product
"SIG" & Cam Color & Cam Color
psig Character P/N* Code Character P/N* Code
Light Olive
3-15 -08000- Yellow -08001- Green
Light Olive
3-9 -08000- Yellow Ranger - -08001- Green
Ranger - Light Linear Olive
9-15 =% -08000- Yellow or -08001- Green
Olive Premier Light
3-7 -08001- Green =% -08002- Gray
Olive Light
7-11 -08001- Green -08002- Gray
Olive Light
11-15 -08001- Green -08002- Gray
TABLE 3
RANGE SPRING SELECTION
* Complete Cashco part number (P/N) is as shown in Figure 7. Table 3 indicates the
missing numbers of the complete P/N; general P/N = 830-69-5-_ _ _ _ _-00.
X
Signal = min
Output Load = min
Valve Position = closed
Inner wall of
baseplate (26)
Signal = max
Output Load = max
Valve Position = open
Characteristic: = %
Actuator Action: ATO-FC
Positioner Action: Direct
RANGER QCT
X ≈ 1/2" ≈ 12.7 mm
31
31
24
Characteristic: = %
Actuator Action: ATO-FC
Positioner Action: Reverse
RANGER QCT
Signal = min
Output Load = max
Valve Position = open
Signal = max
Output Load = min
Valve Position = closed
Inner wall of
baseplate (26)
X
31
31
24
Control Valve Positioner Plug Action Eckardt
Action/Fail Changeover Stem Travel With Signal Fail Action
Position Action Plate Setting Direction Increasing Position
ATO-FC Direct
CW to Close
Opens Closed
CCW to Open
ATC-FO Direct
CW to Close
Closes Open
CCW to Open
ATC-FO Reverse
CW to Close
Opens Closed
CCW to Open
ATO-FC Reverse
CW to Close
Closes
Open
CCW to Open w/o Signal
N
U
N
U
N
U
N
U