Specifications

35
Table 4 — ICVC Display Data (cont)
EXAMPLE 15 — VFD_HIST DISPLAY SCREEN
To access this display from the ICVC default screen:
1. Press .
2. Press .
3. Scroll down to highlight .
4. Press .
5. Scroll down to highlight .
6. Press .
NOTES:
1. All variables with CAPITAL LETTER point names are available for CCN read operation; forcing shall not be supported on maintenance
screens.
2. Limits not defined for status point.
EXAMPLE 16 — WSMDEFME DISPLAY SCREEN
To access this display from the ICVC default screen:
1. Press .
2. Press .
3. Scroll down to highlight .
4. Press .
5. Scroll down to highlight .
6. Press .
NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation; forcing shall not be supported on maintenance
screens.
MENU
SERVICE
CONTROL ALGORITHM STATUS
SELECT
VFD_HIST
SELECT
DESCRIPTION STATUS UNITS POINT
VFD FAULT HISTORY
Values at Last Fault:
Line Current Ph1(R) 0.0-99999.0 AMPS LNAMPS1H
Line Current Ph2(S) 0.0-99999.0 AMPS LNAMPS2H
Line Current Ph3(T) 0.0-99999.0 AMPS LNAMPS3H
Load Current Ph1(U) 0.0-99999.0 AMPS LDAMPS1H
Load Current Ph2(V) 0.0-99999.0 AMPS LDAMPS2H
Load Current Ph3(W) 0.0-99999.0 AMPS LDAMPS3H
Line Voltage Ph1(RS) 0.0-99999.0 VOLTS LNVOLT1H
Line Voltage Ph2(ST) 0.0-99999.0 VOLTS LNVOLT2H
Line Voltage Ph3(TR) 0.0-99999.0 VOLTS LNVOLT3H
Ground Fault Current 0.0-999.0 AMPS GF_AMPSH
Line Frequency 0.0-99.0 Hz LINEFRQH
Line Power Factor 0.00-2.00 LINE_PFH
Line Current Imbalance 0.0-100.0 % LN_IMBIH
Line Voltage Imbalance 0.0-100.0 % LN_IMBVH
Motor Power Factor 0.00-2.00 MOTORPFH
Motor Current Imbalance 0.0-100.0 % MT_IMBIH
Motor Overload 0.0-100.0 % MOTOROVH
Line Active Current 0.0-99999.0 AMPS AMPSACTH
Line Reactive Current 0.0-99999.0 AMPS AMPS_REH
Line Active Voltage 0.0-99999.0 VOLTS VOLTACTH
Line Reactive Voltage 0.0-99999.0 VOLTS VOLT_REH
DC Bus Voltage 0.0-99999.0 VOLTS BUSVOLTH
DC Bus Voltage Reference 0.0-99999.0 VOLTS BUS_REFH
Flux Current 0.0-99999.0 AMPS FLUXAMPH
Torque Current 0.0-99999.0 AMPS TORQAMPH
Inverter Temperature 0.0-300.0 DEG F INVTEMPH
Rectifier Temperature 0.0-300.0 DEG F RECTEMPH
VFD Enclosure Temp 0.0-300.0 DEG F VFDENCLH
VFD Cold Plate Temp 0.0-300.0 DEG F CP_TEMPH
Actual VFD Speed 0.0-100.0 % VFD_ACTH
Comp Motor RPM NOTE 2 RPM CPR_RPMH
Comp Motor Frequency NOTE 2 Hz VFDFREQH
Chiller Fault State 200-225 VFDSTATH
VFD Fault Code 200-225 VFD_FLTH
DESCRIPTION STATUS UNITS POINT
WSM Active? 0/1 NO/YES WSMSTAT
Chilled Water Temp 0.0-99.9 DEG F CHWTEMP
Equipment Status 0/1 OFF/ON CHWRST
Commanded State XXXXXXXX TEXT CHWRENA
CHW setpt Reset Value 0.0-25.0 ^F CHWRVAL
Current CHW Set Point 0.0-99.9 DEG F CHWSTPT
MENU
SERVICE
CONTROL ALGORITHM STATUS
SELECT
WSMDEFME
SELECT