Instruction manual

23
A12187
6.3.1.1. Auto Mode set up
Once the auto changeover option has been selected, touch SAVE.
S Enable or Disable: Choose to enable or disable auto changeover mode
d Default = Ena ble
S Auto changeover time: Adjustable from 5 to 120 minutes
d Default = 30 minutes
6.3.1.2. Heat/Cool Deadband
The minimum difference enforced between heating and cooling desired
temperatures. This can allow one setting to “push” the other to maintain this
difference. When the correct deadband is set, touch SAVE.
S Deadband: Adjustable from 0 to 6_F(0to2_C)
d Default = 2_F
6.3.1.3. Offsets
This option allows calibration (or deliberate miscalibration) of the temperature and
humidity sensors. These offsets are added to the actual temperature/humidity
values. When the correct offsets are made, touch SAVE.