Installation manual
36
5. Mix Totaline environmentally sound coil cleaner in a
2
1
/
2
gallon garden sprayer according to the instruc-
tions included with the cleaner. The optimum solution
temperature is 100°F(38°C).
NOTE: Do NOT USE water in excess of 130°F(54°C),
as the enzymatic activity will be destroyed.
6. Thoroughly apply Totaline
®
environmentally sound
coil cleaner solution to all coil surfaces including the
finned area, tube sheets and coil headers.
7. Hold garden sprayer nozzle close to finned areas and
apply cleaner with a vertical, up-and-down motion.
Avoid spraying in horizontal pattern to minimize po-
tential for fin damage.
8. Ensure cleaner thoroughly penetrates deep into finned
areas.
9. Interior and exterior finned areas must be thoroughly
cleaned.
10. Finned surfaces should remain wet with cleaning
solution for 10 minutes.
11. Ensure surfaces are not allowed to dry before rinsing.
Reapply cleaner as needed to ensure 10-minute satur-
ation is achieved.
12. Thoroughly rinse all surfaces with low velocity clean
water using downward rinsing motion of water spray
nozzle. Protect fins from damage from the spray
nozzle.
13. Replace top cover and rear corner posts.
Service Parts
Listings of service parts for all units are available from the
Replacement Components Division’s Electronic Parts
Information Catalog (EPIC). EPIC is available at Totaline
stores, distributor and service office parts departments and
on-line at HVACPartners.com.
When entering EPIC, the full unit model number is
required. The model number includes the Design Revision
reference value (see Fig. 3, Position 13). The unit model
number is available from the unit’s information data plate.
(Do not use the “catalog number” when using EPIC. The
“catalog number” suppresses the Design Revision value;
failure to include Design Revision value may cause an
incorrect unit parts list to be displayed.) When using
EPIC, enter first four digits of the model number only.
Find appropriate model from sales packages listed. Be
sure to choose correct voltage and Design Revision.
EPIC is a product of RCD. To comment of the EPIC
program, use the “Comment” button inside the EPIC
program.
FASTENER TORQUE VALUES
Table 12 – Torque Values
Compressor mounting bolts 65---75 in–lbs
(734–847 N–cm)
Condenser fan motor mounting bolts 20 ±2in–lbs
(226 ±23 N–cm)
Condenser fan hub setscrew 84 ±2in–lbs
(949 ±136 N–cm)
High-flow service port 96 ±10 in–lbs
(1085 ±23 N–cm)
Schrader-type service check valve 2–3 in–lbs
(23–34 N–cm)
Compressor oil sightglass thread 330 ±31 in–lbs
(23–34 N–cm)
Compressor to Compressor rail torque 120–168 in–lbs
(1356–1898 N–cm)
Compressor rail to base pan torque 70 ±5in–lbs
(791 ±57 N–cm)
38AUQ