Specifications

23
ECONOMIZER SUBMASTER REFERENCE (NOT
USED) — This point displays the supply air temperature deter-
mined by the Economizer PID calculation.
Economizer
Submaster
Reference: Display Units: Degrees F (Degrees C)
Display Range: 48 to 120
Default Value: 120
Network Access: Read Only
ECONOMIZER SUBMASTER GAIN (NOT USED) —
Displays the current Submaster gain multiplier in use to calcu-
late the economizer damper position. At temperatures below
45 F this number will decrease to slow the rate of movement of
the economizer damper.
Economizer
Submaster Gain: Display Range: –20 to 20
Default Value: –5.5
Network Access: Read Only
COMPRESSOR STARTS Displays the total number of
compressor starts.
Compressor
Starts: Default Value: 0
Network Access: Read Only
COMPRESSOR 1 RUN TIME — Displays the number of
run hours of compressor no. 1.
Compressor 1
Run Time: Display Units: Hours
Default Value: 0
Network Access: Read Only
COMPRESSOR 2 RUN TIME — Displays the number of
run hours of compressor 2.
Compressor 2
Run Time: Display Units: Hours
Default Value: 0
Network Access: Read Only
SUPPLY FAN RUN TIME — Displays the number of supply
fan run hours. This is not the same timer used for the filter sta-
tus. A separate timer is used to keep track of the run hours since
the last filter change.
Supply Fan
Run Time: Display Units: Hours
Default Value: 0
Network Access: Read Only
LINKAGE THERMOSTAT — The following Linkage Ther-
mostat points display the standard values received from a
Linkage Thermostat (if one is being used to provide space
temperature, set point and occupancy information).
Linkage
Status: Display Range: 0 to 3
Default Value: 2
Network Access: None
The Supervisory Element displays the address of the device
sending the linkage supervisory table to the PremierLink™
controller.
Supervisory
Element: Default Value: 0
Network Access: Read Only
The Supervisory Bus displays the bus number of the device
sending the linkage supervisory table to the PremierLink
controller.
Supervisory Bus: Default Value: 0
Network Access: Read Only
The Supervisory Block displays the block or table
number of the linkage table occurrence in the supervisory
device. Some linkage supervisory devices may contain
more than one linkage table for different air sources.
Supervisory
Block: Default Value: 0
Network Access: Read Only
The Average Occupied Heat Set Point displays the
Occupied Heat set point from the Linkage Thermostat.
Average Occupied
Heat Set Point: Display Units: Degrees F (Degrees C)
Display Range: 0.0 to 99.9
Default Value: 0.0
Network Access: None
The Average Occupied Cool Set Point displays the Occu-
pied Cool set point from the Linkage Thermostat.
Average Occupied
Cool Set Point: Display Units: Degrees F (Degrees C)
Display Range: 0.0 to 99.9
Default Value: 0.0
Network Access: None
The Average Unoccupied Heat Set Point displays the Unoc-
cupied heat set point from the Linkage Thermostat.
Average Unoccupied
Heat Set Point: Display Units: Degrees F (Degrees C)
Display Range: 0.0 to 99.9
Default Value: 0.0
Network Access: None
The Average Unoccupied Cool Set Point displays the Unoc-
cupied cool set point from the Linkage Thermostat.
Average Unoccupied
Cool Set Point: Display Units: Degrees F (Degrees C)
Display Range: 0.0 to 99.9
Default Value: 0.0
Network Access: None
The Average Zone Temperature displays the space tempera-
ture from the Linkage Thermostat.
Average Zone
Temperature: Display Units: Degrees F (Degrees C)
Display Range: 0.0 to 99.9
Default Value: 0.0
Network Access: None
The Average Occupied Zone Temperature displays the
space temperature from the Linkage Thermostat during occu-
pied periods.
Average Occupied
Zone Temperature: Display Units: Degrees F (Degrees C)
Display Range: 0.0 to 99.9
Default Value: 0.0
Network Access: None
The Occupancy Status point displays a 1 if occupancy is re-
ported by the Linkage Thermostat. The Occupancy Status
point displays a 0 if occupancy is not reported by the Linkage
Thermostat.
Occupancy
Status: Display Range: 0, 1
Default Value: 0
Network Access: None