Specifications
21
MODE — The Mode point displays the current occupied
mode for the controller. If the controller is following its own
local schedule this is the result of the local schedule status. If
the controller is configured to follow a global schedule, this
point displays the mode last received from a global schedule
broadcast.
Mode: Display Range: 0 to 1
Default Value: 0
Network Access: None
CURRENT OCCUPIED PERIOD — If the controller is con-
figured to determine occupancy locally, the Current Occupied
Period point is used to display the current period determining
occupancy.
Current Occupied
Period: Display Range: 1 to 8
Default Value: 0
Network Access: None
OVERRIDE IN PROGRESS — The Override in Progress
point is used to display if an occupancy override is in progress.
The point will display “Yes” if an override is in progress, or
“No” if there is no override.
Override In
Progress: Display Range: Yes/No
Default Value: No
Network Access: None
OVERRIDE DURATION — The Override Duration point
displays the number of minutes remaining for an occupancy
override that is in effect. If the override duration value down-
loaded is in hours, the value will be converted to minutes. If the
occupancy schedule is occupied when override is initiated, the
current occupancy period will be extended by the number of
hours/minutes requested.
If the current occupancy period is unoccupied when the oc-
cupancy override is initiated, the mode will change to occupied
for the duration of hours/minutes downloaded. If the occupan-
cy override is due to end after the start of the next occupancy
period, the mode will transition from occupancy override to oc-
cupied without becoming unoccupied, and the occupancy over-
ride timer will be reset.
Override
Duration: Display Units: Minutes
Display Range: 0 to 240
Default Value: 0
Network Access: None
OCCUPIED START TIME — The Occupied Start Time
point shows the time that the current occupied mode began. If
the current mode is unoccupied or the controller is following a
global schedule, the value displayed by this point will remain at
default.
Occupied
Start Time: Display Range: 00:00 to 24:00
Default Value: 00:00
Network Access: None
UNOCCUPIED START TIME — The Unoccupied Start Time
point shows the time that the current occupied mode will end.
This will also be the beginning of the next unoccupied mode. If
the current mode is unoccupied or the controller is following a
global schedule, the value displayed by this point will remain at
default.
Unoccupied
Start Time: Display Range: 00:00 to 24:00
Default Value: 00:00
Network Access: None
NEXT OCCUPIED DAY — The Next Occupied Day point
displays the day of the week when the next occupied period
will begin. This point is used with the Next Occupied Time so
the user will know when the next occupied period will occur. If
the controller is following a global schedule this point will
remain at default.
Next Occupied
Day: Display Range: MON, TUE, WED,
THU, FRI, SAT, SUN
Default Value: No display (Blank)
Network Access: None
NEXT OCCUPIED TIME — The Next Occupied Time point
displays the time of day when the next occupied period will
begin. This point is used with the Next Occupied Day so the
user will know when the next occupied period will occur. If the
PremierLink™ controller is following a global schedule this
point will remain at default.
Next Occupied
Time: Display Range: 00:00 to 24:00
Default Value: 00:00
Network Access: None
NEXT UNOCCUPIED DAY — The Next Unoccupied Day
point displays the day of the week when the next unoccupied
period will begin. This point is used with the Next Unoccupied
Time so the user will know when the next unoccupied period
will occur. If the controller is following a global schedule this
point will remain at default.
Next Unoccupied
Day: Display Range: MON, TUE, WED,
THU, FRI, SAT, SUN
Default Value: No display (Blank)
Network Access: None
NEXT UNOCCUPIED TIME — The Next Unoccupied Time
point displays the time of day when the next unoccupied
period will begin. This point is used with the Next Unoccupied
Day so the user will know when the next unoccupied period
will occur. If the controller is following a global schedule this
point will remain at default.
Next Unoccupied
Time: Display Range: 00:00 to 24:00
Default Value: 00:00
Network Access: None
LAST UNOCCUPIED DAY — The Last Unoccupied Day
point displays the day of the week when the controller last
changed from occupied to the Unoccupied mode. This point is
used in conjunction with the Last Unoccupied Time to know
the last time and day when the controller became unoccupied.
If the controller is following a global schedule this point will
remain at default.
Last Unoccupied
Day: Display Range: MON, TUE, WED,
THU, FRI, SAT, SUN
Default Value: No display (Blank)
Network Access: None
LAST UNOCCUPIED TIME — The Last Unoccupied Time
point displays the time of day when the controller last changed
from occupied to the Unoccupied mode. This point is read in
conjunction with the Last Unoccupied Day to know the last
time and day when the controller became unoccupied. If the
controller is following a global schedule this point will remain
at default.
Last Unoccupied
Time Display Range: 00:00 to 24:00
Default Value: 00:00
Network Access: None