Specifications

2
SUPPLY AIR TEMPERATURE SENSOR — A factory-
installed supply air temperature sensor is provided with
PremierLink™ controller for the water source heat pump
equipment. The sensor is a 10k ohm thermistor, which is
installed in and protected by a stainless steel housing probe.
Probe size is
1
/
4
in. diameter by 1.5 in. long. Wire size and type
are 22 AWG (American Wire Gage), 7/30 copper wire, and
PVC white, 2 conductors.
LEAVING WATER TEMPERATURE SENSOR — A factory-
installed leaving water temperature sensor is provided with
PremierLink controller for the water source heat pump equip-
ment. The sensor is a 10k ohm thermistor, which is installed in
and protected by a stainless steel housing probe. Probe size is
1
/
4
in. diameter by 1.5 in. long. Wire size and type are 22 AWG,
7/30 copper wire, and PVC white, 2 conductors.
Field-Supplied Hardware —
The PremierLink control-
ler is configurable with the following field-supplied sensors:
space temperature sensor (33ZCT55SPT, 33ZCT56SPT, or
33ZCT58SPT) in sensor mode or thermostat mode for
economizer control
indoor air quality sensor (33ZCSENCO2, 33ZCT55CO2,
33ZCT56CO2) required only for demand control
ventilation
For specific details about sensors, refer to the literature
supplied with the sensor.
SPACE TEMPERATURE (SPT) SENSOR — A field-supplied
Carrier space temperature sensor is required to maintain the
space temperature in sensor mode. There are three sensors avail-
able for this application:
33ZCT55SPT, Space Temperature Sensor with Override
Button
33ZCT56SPT, Space Temperature Sensor with Override
Button and Set Point Adjustment
33ZCT58SPT, Communicating Room Sensor with Override
Button, Set Point Adjustment, and Manual Fan control
INDOOR AIR QUALITY CO
2
SENSOR An indoor air
quality sensor is required for CO
2
level monitoring. Three
different CO
2
sensors are available for this application:
33ZCSENCO2 sensor is an indoor, wall-mounted sensor
with an LED (light-emitting diode) display
33ZCT55CO2 sensor is an indoor, wall-mounted sensor
without display. The CO
2
sensor also includes a space tem-
perature sensor with override button
33ZCT56CO2 sensor is an indoor, wall-mounted sensor
without display. The CO
2
sensor also includes a space tem-
perature sensor with override button and temperature offset
Y
W
O
G
R
C
AL1
AL2
A
CR
CMP1
FAN
PWR
HS1/EXH/RVS
PREMIER
LINK
CR
COMPLETE
C
CONTROL
J4
J6
J5
J8
J1
PWR
S
P
S
A
L
W
CMPSAFE
T
T
T
LEGEND
NOTE: Reversing valve is on in Cooling mode.
CR Control Relay
LWT Leaving Water Temperature Sensor
SAT Supply Air Temperature Sensor
SPT Space Temperature Sensor
Fig. 1 — Typical Factory-Installed PremierLink Wiring for WSHP Units
(Except SPT Sensor — Field Installed)