Specifications

18
CONTINUOUS POWER EXHAUST (NOT USED) — The
Continuous Power Exhaust function defines the operation of
the Power Exhaust Fan.
If disabled, the Power Exhaust Fan will operate during
economizer purge cycles when the economizer damper posi-
tion is above the configured minimum value. If enabled, the
Power Exhaust Fan will follow the supply fan's operation.
Continuous
Power
Exhaust: Range: Disable/Enable
Default Value: Disable
SUPPLY FAN STATUS ENABLE The Supply Fan Status
Enable function is enabled when an actual sensor input is used
to determine that the supply fan is on. If the supply fan status is
OFF when the fan should be running, Heat, Cool and Econo-
mizer will be disabled.
If this decision is disabled, the Supply Fan Status will fol-
low the state of the Supply Fan Relay in order to allow the
algorithms to run that depend on the Supply Fan Status to be
ON before executing.
Supply Fan
Status Enable: Range: Disable/Enable
Default Value: Disable
MAXIMUM OFFSET ADJUSTMENT — Maximum Offset
Adjustment value determines the degree in which the occupied
heating and cooling set points can be adjusted by the setpoint
adjustment slide bar on the space temperature sensor.
Max Offset
Adjustment: Units: Delta Degrees F
(Delta Degrees C)
Range: 0.0 to 15.0
Default Value: 2.0
SPACE TEMPERATURE TRIM — The Space Temperature
Trim configuration is used to calibrate the temperature display
for a sensor that does not appear to be reading correctly.
Space Temperature
Trim: Units: Delta Degrees F
(Delta Degrees C)
Range: –9.9 to 9.9
Default Value: 0.0
SUPPLY AIR TEMPERATURE TRIM — The Supply Air
Temperature Trim configuration is used to calibrate the temper-
ature display for a sensor that does not appear to be reading
correctly.
Supply Air
Temperature
Trim: Units: Degrees F (Degrees C)
Range: –9.9 to 9.9
Default Value: 0.0
PremierLink Configuration Screen
The Pre-
mierLink Configuration screen allows the user to configure all
functions. See Table 13.
OPERATING MODE — The Operating Mode function
determines the operating mode of the PremierLink controller.
There are two operating modes from which to choose: TSTAT
and CCN Sensor.
The TSTAT mode allows PremierLink controller to operate
as a stand-alone thermostat control by monitoring Y1 (cooling
stage 1), Y2 (cooling stage 2), W1 (heating stage 1), W2 (heat-
ing stage 2), and G (indoor fan) inputs.
The CCN mode allows the controller to integrate into a
Carrier Comfort Network.
Operating Mode: Range: 0 for TSTAT
1 for CCN
Default Value: 0 (TSTAT)
Table 13 PremierLink Control Configuration
HEAT TYPE (NOT USED) — The Heat Type mode deter-
mines the type of heat equipment the controller uses. There are
two choices: gas or electric.
Heat Type: Range: 0 for Gas
1 for Electric Heat
Default Value: 0 (Gas)
UNIT TYPE The Unit Type mode determines the type of
heating/cooling equipment the controller is attached to. There
are two choices: AC or Heat Pump.
The AC mode is primarily used for units using the compres-
sors for cooling only.
The Heat Pump mode is primarily used for units using a
heat pump (for example, compressors for heating and cooling).
Unit Type: Range: 0 for AC
1 for Heat Pump
Default Value: 1 (Heat Pump)
Staging is as follows for gas electric units (AC = 0), Carrier
heat pumps with a defrost board (AC = 1), or cooling units with
electric heat (AC = 0 or 1 and HEATYPE = 1):
If Heating PID STAGES = 2
(HCAP = 50% capacity) energized HS1.
(HCAP = 100% capacity) energizes HS2.
If Heating PID STAGES = 3 and AUXOUT = HS3
(HCAP = 33% capacity) energizes HS1
(HCAP = 66% capacity) energizes HS2
(HCAP = 100% capacity) energizes H3_EX_RVS
DESCRIPTION VALUE UNITS NAME
0=TSTAT, 1=CCN Sensor 0 TSTATCFG
0=Gas, 1=Electric Heat
(Not Used)
0
HEATTYPE
0=AC Unit, 1=Heat Pump 1 AC
Auxiliary Output 3 AUXOUT
0=None
1=Exhaust Fan
2=Heat Stage
3=Reversing Valve
Unoccupied Free Cool
(Not Used)
Disable
NTEN
Demand Limiting Disable DLEN
Loadshed Group Number 1 LSGP
CCN Broadcast OAT, ENTH,OAQ 0 OATBC
Global Schedule Broadcast No GSBC
Broadcast Acknowledge No BCACK
Schedule Number 64 SCHEDNUM
Timed Override Hours 0 hours TIMOVRID
Linkage Thermostat
Cool Strt Bias(min/deg) 10 min KCOOL
Heat Strt Bias(min/deg) 10 min KHEAT
Filter Timer hrs* 100 15 FIL_TIMR
IAQ Priority Level Low IAQP
IAQ Pre-Occupancy Purge Disable IAQPURGE
IAQ Purge Duration 5 min IQPD
IAQ Delta Setpoint 650 IAQD
IAQ Maximum Damper Pos. 50 %IAQMAXP
Indoor AQ Low Ref. 0.0 IIAQREFL
Indoor AQ High Ref. 2000.0 IIAQREFH
Outdoor AQ Low Ref. (Not Used) 0.0 OIAQREFL
Outdoor AQ High Ref. (Not Used) 2000.0 OIAQREFH
Outdoor AQ Lockout Point
(Not Used)
0
OIAQLOCK
Service Password 1111 PASSWORD
Password Enable Disable PASS_EBL
Metric Display Off DISPUNIT